Brochure

1-150.11
20
Table 20.1
Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F
Entering Air – High Motor Speed
Water Data Air Data Motor Data
Pressure Maximum Heat Throw
Drop Sound Mounting or Spread Outlet Final Air
Model (Ft. of Min/Max Class Height @ Max. Velocity Temp. Approx.
Type No. Btu/hr. GPM Water) GPM (ft.) Height Cfm (Fpm) (°F) Hp RPM
HSB/HC-18L 11,300 1.2 0.4 0.25 / 5.0 II 10 21 364 650 88 1/60 1550
HSB/HC-24L 13,700 1.4 0.6 0.25 / 5.0 II 12 22 435 775 88 1/25 1550
HSB/HC-33L 19,300 2.0 0.2 0.4 / 10.0 II 13 26 695 730 85 1/25 1550
HSB/HC-47L 21,100 2.2 0.2 0.4 / 10.0 III 15 34 855 890 82 1/12 1550
HSB/HC-63L 37,900 4.0 0.4 0.5 / 20.0 III 17 35 1170 695 89 1/12 1550
Horizontal HSB/HC-86L
44,600 4.6 0.6 0.5 / 20.0 III 18 38 1510 890 87 1/8 1625
Delivery HSB/HC-108L 66,100 6.9 1.8 0.8 /
30.0 III 20 38 2150 815 88 1/8 1625
HSB/HC-121L 66,700 6.9 1.9 0.8 / 30.0 III 19 31 2070 785 89 1/5 1075
HSB/HC-165L 113,200 11.8 6.6 2.0 / 30.0 IV 22 48 3480 920 89 1/3 1075
HSB/HC-258L 147,400 15.4 3.2 2.5 / 70.0 V 23 54 4655 735 89 1/2 1075
HSB/HC-290L 161,100 16.8 3.7 2.5 / 70.0 V 24 56 5040 800 89 1/2 1075
HSB/HC-340L 200,900 20.9 6.6 2.5 / 70.0 V 24 56 5575 760 93 1/2 1075
Power-
PT/PTN-
Throw
610L
V/VN-42L 23,000 2.4 0.4 0.5 / 10.0 II 14 18 21 14 960 835 83 1/30 1050
V/VN-59L 32,600 3.4 0.3 0.75 / 15.0 II 17 23 26 17 1190 1035 86 1/30 1050
V/VN-78L 43,600 4.5 0.3 1.0 / 20.0 II 20 28 31 21 1740 1170 84 1/15 1050
V/VN-95L 53,100 5.5 0.3 1.25 / 25.0 II 20 28 31 21 1760 1180 89 1/15 1050
V/VN-139L 81,200 8.5 1.6 1.0 / 30.0 III 24 33 37 25 2860 1380 87 1/5 1075
V/VN-161L 93,900 9.8 1.3 1.25 / 40.0 IV 28 37 41 28 3400 1640 86 1/3 1075
Vertical V/VN-193L 112,500 11.7 1.3 1.5 / 50.0 IV 29 38 44 29 3710 1790 89 1/3 1075
Delivery V/VN-212L 123,400 12.9 0.9 2.0 / 60.0 IV 29 38 44 29 3,830 1845 91 1/3 1075
V/VN-247L 143,600 15.0 1.2 2.0 / 60.0 V 34 45 51 35 5110 2030 87 1/2 1075
V/VN-279L 162,200 16.9 1.2 2.25 / 75.0 V 38 48 57 39 5790 2300 87 1/2 1075
V/VN-333L 198,300 20.7 2.3 2.25 / 75.0 V 38 48 57 39 6340 2300 90 3/4 1140
V/VN-385L 229,100 23.9 3.0 2.25 / 75.0 VI 38 46 57 49 8140 1970 87 1 1140
V/VN-500L 295,000 30.7 2.8 3.0 / 100.0 VI 48 57 72 49 11,000 2670 85 1-1/2 1140
V/VN-610L 344,900 35.9 0.6 6.0 / 100.0 VI 47 55 70 48 12,400 2445 86 1-1/2 1140
V-952L 546,700 56.9 0.7 14.0 / 100.0 VI 48 61 72 68 12,800 2440 102 2 1140
Table 20.2
Performance Data for Low Outlet Temperature Units at Standard Conditions of 200°F Entering Water and 60°F
Entering Air – Reduced Motor Speeds
Water Data Air Data Motor Data
Pressure Maximum
Drop Sound Mounting Heat Throw Outlet Final Air
Model (Ft. of Class Height @ Max. Velocity Temp. Approx.
Type No. Btu/hr. GPM Water) (ft.) Height Cfm (Fpm) (°F) Hp RPM
HSB/HC-18L 8700 1.2 0.4 I 10 13 230 410 94 1/60 1000
HSB/HC-24L 10,400 1.4 0.6 I 12 14 265
475 95 1/25 1000
Horizontal HSB/HC-33L 14,700 2.0 0.2 I 13 15 430
455 91 1/25 1000
Delivery HSB/HC-47L 16,300 2.2 0.2 II 15 20 540
570 87 1/12 1000
HSB/HC-63L 29,000 4.0 0.4 II 17 21 725
435 96 1/12 1000
HSB/HC-86L 33,900 4.6 0.6 II 18 23 925
550 93 1/8 1000
HSB/HC-108L 50,500 6.9 1.8 II 20 23 1330
510 94 1/8 1000
Horizontal units with horizontal louvers open 30° from vertical plane. Vertical types equipped with cone jet deflector, blades fully opened are shown in bold. Non-bolded
mounting height/spread data is for units without deflectors. Please see page 22 for additional outlet accessory performance data.
Cfm for
horizontal types is entering Cfm. Cfm for vertical and Power-Throw
types is leaving Cfm.
V and PT models have copper tubes, VN and PTN models have 90/10 cupro-nickel tubes.
See page 8 for Sound Class definitions.
Requires Solid State Motor Speed Controller.
PERFORMANCE DATA
Hot Water Performance Data - Low Outlet Temperature Models
344,900 35.9 0.6 6.0 / 100.0 VI 23 164 12,400 2445 86 1-1/2 1140