Service manual

2. Overhauling
2-5
A A section (coupling) details
SG05046
2.3
Disassembly/Reassembly of Generator Main Unit and Connection
of Generator Main Unit and Engine
2.3.1 Disassembly of generator main unit
The generator main unit is unilaterally mounted and the clearance is small, so it must
be handled with extreme care to avoid the possibility of damage to the rotor or stator.
Use hoisting equipment of sufficient capacity when it is necessary to lift up the engine
and the generator main unit.
Lifting weight
Unit : lbs (kg)
SDG25S
-6A7
SDG45S
-6A6
SDG65S
-6A6
SDG100S
-6A6
SDG125S
-6A6
SDG150S
-6A6
Weight of generator
main unit
320 (145) 452 (205) 595 (270) 794 (360) 980 (445) 1,224 (555)
Weight of engine
392 (178) 550 (250) 810 (368) 1,036 (470) 1,500 (680) 1,500 (680)
Generator main unit
Engine
Bolts (for coupling of
the engine flywheel
and the generator
coupling)
Bolts (for connection of
the engine flywheel
housing and the
generator main unit
frame)