Service manual
4. Troubleshooting
4-11
[C] Measurement of Insulation Resistance of Generator Winding Wires
Measurement is performed with a 500V megger. The situation is considered to be satisfactory if the
measurement produces a result of 1M or more, while a result of less than that value indicates
failure.
Voltage selection switch position 480/277V
6-17-1
(1) Generator armature winding wires
● (Procedure)(Megger tester required)
1. Remove the load side cable from the output
terminal board.
2. Remove the cable between the terminal "N" and
terminal "Ground" which are connected on the
back of the output terminal plate.
3. Remove the AVR connector inside the generator
control panel.
4. Switch ON the three-phase breaker, and then
measure each insulation resistance between the
terminals L1, L2, L3 terminal and bonnet.
5. Insulation resistance when measured with a
500V megger tester must be above 1 MΩ.
6. After finishing the measurement of insulation
resistance, re-connect the cable between the
terminal "N" and terminal "Ground".
After making sure that the insulation resistance of
the generator is higher than 1 MΩ, be sure to
re-connect the cable between the terminal "N" and
terminal "Ground" just as it was originally
connected. If it is left disconnected, the grounding
becomes imperfect so that it could cause electric
shock.
A040180-1
A040179
SDG45S/65S-6A6
Bonnet
A
VR Connector