SVZ-KP Operation Manual
7. Specifications
SVZ-KP NA Series
Small Cabinet Medium Cabinet
Item / Model SVZ-KP12NA SVZ-KP18NA SVZ-KP24NA SVZ-KP30NA SVZ-KP36NA
Power Source 208/230V, 1-phase, 60hZ
Cooling capacity/Heating capacity
Btu/h 12,000 / 13,500 18,000 / 22,800 24,000 / 27,000 30,000 / 34,000 36,000 / 40,000
kW 3.5/4.0 5.3/6.7 7.0 / 7.9 8.8 / 10.0 10.6 / 11.7
Tonnage 1 1.5 2 2.5 3
Dimensions
Height mm [in] 1,101 [39-3/4] 1,113.8 [43-7/8]
Width mm [in] 432 [17]
Depth mm [in] 548 [21-5/8]
Net weight kg [lb] 43 [93] 54 [119]
Fan
Airflow rate
(Low-Mid-High)
CFM 314 – 381 – 448 471 – 573 – 675 515 - 625 - 735 613 - 744 - 875 767 - 931 - 1,095
External static
pressure
in. WG 0.30 - 0.50 - 0.80
[Pa] [75 - 125 - 200]
Sound Pressure
(Low - Mid - High)
dB(A) 29 - 34 - 37 31 - 35 - 39 30-34-38 32-36-40 35-39-43
Notes:
1. Rating conditions (cooling)
Indoor : 80 °F [26.7 °C] D.B., 67 °F [19.4 °C]
W.B.
Outdoor : 95 °F [35 °C] D.B.
2. Rating conditions (heating)
Indoor : 70 °F [21.1 °C] D.B.
Outdoor : 47 °F [8.3 °C] D.B., 43 °F [6.1 °C]
W.B.
3. The indicated capacity is the value when one
indoor unit is connected to the outdoor unit.
4. Specifications subject to change without notice.
5. The external static pressure is set to 0.50 in.
WG (125 Pa) at factory shipment.
Table 1. Guaranteed operating range
Indoor
Cooling
Upper limit
95 °F [35 °C] D.B.
71 °F [21.7 °C] W.B.
Lower limit
67 °F [19.4 °C] D.B.
57 °F [13.9 °C] W.B.
Heating
Upper limit
80 °F [26.7 °C] D.B.
-
Lower limit
70 °F [21.1 °C] D.B.
-
1. Units should be installed by licensed electric contractor accordingly to local code requirement.
2. For outdoor units to be connected, refer to the Installation Manual that comes with the units.
SVZ-KP12,18, 24, 30, 36NA
15 © 2018 Mitsubishi Electric US, Inc.
ENGLISH