SVZ-KP Operation Manual

3. Operation
About the operation method, refer to the operation manual that comes with each remote controller.
3.1 Operation mode select
Cool/DRY/Fan/Heat/Automatic (cool/heat)/Ventilation modes are available.
NOTE
Heat and Automatic modes can not be available for cooling only units.
Ventilation mode: only indicated on the following condition. Wired remote controller is
used and LOSSNAY is connected.
Automatic mode
According to a set temperature, cooling operation starts if the room temperature is too
hot and heating operation starts if the room temperature is too cold.
During automatic operation, if the room temperature changes and remains 4 °F [2 °C]
or more above the set temperature for 15 minutes, the air conditioner switches to
cooling mode. If the room temperature remains 4 °F [2 °C] or more below the set
temperature for 15 minutes, the air conditioner switches to heating mode.
Cooling mode
15 minutes (switches from
heating to cooling)
Set temperature +4 °F [2 °C]
Set temperature
Set temperature -4 °F [-2 °C]
15 minutes (switches
from cooling to heating)
SVZ-KP12,18, 24, 30, 36NA
Specifications are subject to change without notice. 8
ENGLISH