Specifications

ME96 Super-S Series Features
Impressive Monitoring Functions
Advanced Alarm Display
Motor Starting Current Mask
Succeeded Display Functions
Large Bar Graph Display
Special Display
Max/Min Display Function
High-brightness Backlight
Note: Alarm indicator blinks when it is set on alarm mode.
(1) Bar Graph Fixed Display
(2) Digital Values Display by Bar Graph
»Bar Graph Display
Each measuring items can be displayed by a bar graph. With bar graph display, one can grasps the rated value and percentage
against the alarm value instantly.
Measuring items can be displayed by bar graph. The mark indicates that display is fixed.
Furthermore, the
+
and
buttons can be used to change the display between items measured.
Values on the tri-level digital display can be shown by bar graphs (Except when the tri-level display is measuring the same items).
Bar graph shows the digital value of
»Maximum/Minimum Value Display
The maximum and minimum value of each measuring items can be displayed. Since the max/min display shows the current value as
well as max/min values, the display can be used for monitoring. Also,range of minimum value to maximum value is shown by bar graph.
Alarm indicator
Value shown by bar graph
Alarm
indicator
»Special Display by Display Pattern P00
Display can be selected as desired Display Pattern P00.
»High-reliability and high-brightness backlight is built in
»Backlight brightness can be adjusted from level 1 to 5 (default setting is 3)
»“Always-on mode” or “Automatic off mode” can be selected (default
setting is automatic off mode)
ME96NS Series ME96SS Series
Upper/Middle/Lower levels: Select from A, DA, V, W, var, VA, PF, Hz, Wh, -Wh, varh, VAh
Maximum of four displays can be set
(1) Backlight blinks when an alarm occur.
(2) Automatic or manual alarm cancel can be selected.
(3) Upper/lower limits of up to four points can be monitored.
(4) Alarm output delay time can be set.
Time of alarm output after the maximum value and minimum value is reached can be
set. With this function,alarm output caused by frequency change at start-up current of
a motor and start-up of private power generating facility can be avided. Furthermore,
maximum value and minimum value do not update during alarm delay.
Current
Time
Upper limit
value
Lower limit
value
Motor
starting
current
Alarm Delay
Time
Alarm Delay
time
No alarm output and
maximum/minimum
value update during
alarm delay time
Alarm
generation
No lower limit alarm on 0A, 0V
During motor current monitoring, this function
can be used to prevent updating the
maximum value and alarm output. Although
the maximum value is not updated, the
current value is displayed. The starting
current mask time can be set in the range
from 1s to 5min.
<Starting current mask>
The maximum values for current and
power are not updated during the
starting current mask time.
Furthermore, the alarm is not
activated even if the upper limit alarm
value is exceeded.
<Starting current detection>
The starting current mask
time starts when the current
exceeds the starting current
threshold value.
Current
value
Starting current mask time
Starting
current
Current upper limit alarm value
Starting current threshold value
Time
Note: Set the starting current threshold to a value lower than the lower limit value in consideration of
fluctuations in load current during operation.
Minimum Value Update
Maximum Value Update
5 6