Specifications
Outline
ME96 Super-S Series Features
Expand Line-up
»Measuring accuracy of items such as current, voltage and active energy has been improved.
• current/voltage ±0.1%
• active energy class 0.5s
• Harmonics 1
st
to 31
st
»Functions added for measuring Single phase 2-wire and Single phase 3-wire
»Functions added for measuring Three phase 3-wire system star circuits and 400V direct connections
Three Model Line-up
Enhanced Measuring Functions
Improved Measuring Accuracy
ME96SSH-MB
(High-spec class)
ME96SSR-MB
(Standard class)
ME96SSE-MB
(Economy class)
MODBUS
®
RTU communication
Plug-in module (options)
• Analog/Pulse/Contact output/input
• CC-Link communication
• Digital input/output
(for MODBUS
®
RTU communication)
MODBUS
®
RTU communication
Plug-in module (options)
• Analog/Pulse/Contact output/input
• CC-Link communication
• Digital input/output
(for MODBUS
®
RTU communication)
MODBUS
®
RTU communication
A, DA, V = ±0.1%
W, var, VA, Hz = ±0.2%
PF = 1.0%
Wh = class 0.5s (IEC 62053-22)
varh, Vah = class 2.0 (IEC 62053-23)
Harmonics = 31
st
-deg (max)
Rolling demand
A, DA, V = ±0.2%
W, var, VA, Hz = ±0.5%
PF = 2.0%
Wh = class 1.0 (IEC 62053-21)
varh = class 2.0 (IEC 62053-23)
Harmonics = 13
th
-deg (max)
A, V = ±0.5%
W, Hz = ±0.5%
PF = 2.0%
Wh = class 1.0 (IEC 62053-21)
Optional Plug-in Modules
Note: Optional Plug-in Module can not be used with ME96SSE-MB.
Model name
ME-4210-SS96
ME-0040C-SS96
ME-0052-SS96
Analog output
4
—
—
Pulse/Alarm output
2
—
—
Contact input
1
4
5
Contact output
—
—
2
Transmission function
—
CC-Link
—
Used with
ME96SSH-MB
ME96SSR-MB
Single phase 2-wire
Three phase 3-wire
system (star circuit)
Single phase 3-wire
CC-Link System (ME96SSH-MB/ME96SSR-MB with ME-0040C-SS96 (optional plug-in module))
»Optimum transmission system for remote monitoring using Mitsubishi PLC
»Remote monitoring of contact signal leading to less wiring, less spacing
»Digital unit signal can be latched for over 30ms, and there is no need for external latch circuits
Abnormal Signal (Facility)
Abnormal Signal (Earth Leakage)
Abnormal Signal (Temperature)
Circuit Breaker Status Signal, etc.
<CC-Link Interface>
• Max. Baud rate: 10Mbps
•
Max. Connection Distance: 100m (10Mbps)~1,200m (156kbps)
• Max. Connection Units: 42
• Digital Input: 4 points (24VDC)
CC-Link
CC-Link IE
MELSEC Series
Analog/Pulse/Alarm Output System (ME96SSH-MB/ME96SSR-MB with ME-4210-SS96 (optional plug-in module))
»Remote monitoring of A, DA, V, W, var, VA, PF, Hz, Harmonics Current RMS value
and Harmonics voltage RMS value at 4 to 20mA output (max.4 outputs)
»
Active energy, reactive energy,apparent power and periodic energy (ME96SSH-MB)
can be monitored by pulse output (max.of 2 pulse)
»Can remotely monitor upper/lower limit alarm by contact output (max.1 point)
<Analog output specifications>
• 4-20mA
• 4 outputs
• Resistance load 600Ω or less
<Pulse output specifications>
• No-voltage a contact point
• 35VDC, 0.1A
•
Select output from pulse widths of 0.125, 0.5 or 1s
<Alarm output specifications>
• No-voltage a contact point
• 35VDC, 0.1A
<Digital input specifications>
• 1 point (24VDC)
CC-Link IE
Analog output
Pulse output
Alarm output
MODBUS
®
RTU System (ME96SSH-MB/ME96SSR-MB with ME-0052-SS96 (optional plug-in module))
Central monitor
RS485/USB
converter
RS485 (MODBUS
®
RTU)
USB
»MODBUS
®
RTU communication system optimizes computer monitoring operations
»Attachment of ME-0052-SS96 (optional) enables remote monitoring of the contact input signal
and on/off control of the contact output signal
»Digital input signals can be latched for over 30ms, and there is no need for external latch
circuits
ME-0052-SS96
optional unit
SHT(OFF)
CC(ON)
AL
PAL
TAL
ACB status
<MODBUS
®
RTU Interface Specifications>
• Max. Baud rate: 38.4kbps
• Max. Connection Distance: 1,200m
• Max. Connection Units: 31
<Optional Plug-in Module ME-0052-SS96>
• Digital Input: 5 points (24VDC)
• Digital Output: 2 points (35VDC)
Model name Transmission/Option specifications Main measurement items
400V
400V
400V
21
U
V
u
v
P2
P3
T/R−
T/R+
T/R+
T/R−
MA
MB
SLD
SLD
Ter
Protective
Earthing
MODBUS
®
RTU
Communication
PN
C2
+C1
C1
+C2
+C3
C3
P1
k
K
L
Load
l
Auxiliary power
(+)
(−)
P2
P3
T/R−
T/R+
T/R+
T/R−
MA
MB
SLD
SLD
Ter
PN
C2
+C1
C1
+C2
+C3
C3
P1
MODBUS
®
RTU
Communication
Protective
Earthing
MODBUS
®
RTU
Communication
k
K
L
201
Load
Auxiliary power
(+)
(−)
l
K
L
k
l
3 4