Specifications

Installation position
Protective sheet
Dimensions
Wiring
(when optional unit is attached)
ME96SSH-MB, ME96SSR-MB
ME96SSE-MB
Optional Plug-in Module
25.2
17.1
75.8
61.3
46.8
81.2
88.8
Mounting
1 Dimension of panel
2 View Angle
3 Attachment
4 Installing Optional Plug-in Module
The contrast of the display changes at view angle. Mount it at the position that is
easy to see.
Panel hole dimensions are as shown in the following figure.
It can be attached to a panel with thickness of 1.6 to 4.0mm.
For attachment of the basic device into the panel hole, attach according to the following procedure.
q
The attachment lug is installed in two holes of the top and bottom of the basic device.   
w
Tighten the screws of the lug, and fix onto the panel.
When installing the optional plug-in module onto the basic device, install accoroding to the following procedure.
qRemove the optional cover.
Fit the protruding part of the optional unit into
the slot in the main unit.
Viewing angle
60°
10°
60°
60°
(overhead view)(side view)
Note
92
+ 0.5
0
92
+ 0.5
0
1 Applicable Cable Size
The table on the right describes
the applicable wire size.
Auxiliary power supply, voltage
input, MODBUS
®
RTU
communication terminal
Current input terminal
Optional unit terminal
Part Screw type
Screwless
Screwless
Screwless
Wire specifications
2 Wiring
Main Unit Input/Output Terminal
3 Confirmations
After wiring, make sure the following:
All wiring is connected
There is no misitake in wiring
Optional Plug-in Module Terminal
Lever
Wire insertion hole
Main Unit Terminal
Wiring Diagrams
Three phase 4-wire system: Direct input
qAuxiliary power supply:
100-240VAC or VDC
wFuse: 0.5A
*1 For low-voltage circuits,
secondary-side grounding of
instrument-use voltage/current
transformers is not required.
*2 Connection to NC terminal is
prohibited.
qAuxiliary power supply:
100-240VAC or VDC
wFuse: 0.5A
*1 For low-voltage circuits,
secondary-side grounding
of instrument-use
voltage/current
transformers is not
required.
*2 Connection to NC terminal
is prohibited.
If installing the unit at the panel edge, choose an installation position where there is sufficient space for wiring work.
Optional unit
There is a protective sheet covering the LCD screen to prevent scratching during panel installation. Please remove the sheet
before using the meter. When removing the sheet, the LCD may turn on due to the static electricity generated. This is not
abnormal; the LCD will turn off after a short time.
Turn the auxiliary power supply off before attaching the optional unit. If attached with the power on, the main unit will not
recognize the optional unit. To remedy this, turn off/restart the auxiliary power supply or execute the “instrument restart” operation.
Note
qRemove the wire casing at the end of the
wire and solder to the rod terminal.
wWith the lever pushed in, insert the wire and
then release the lever to connect.
Single-line, stranded-line: AWG24~14 (combined use of rod terminals possible for stranded-line applications)
Notes 1. AWG 24~18 can be used when compliance with UL standards is required.
No
tes 2. Rod terminals cannot be used when compliance with UL standards is required.
Single-line, stranded-line: AWG24~14 (combined use of rod terminals possible for stranded-line applications)
Notes 1.
AWG 22~16 can be used for single-line applications when compliance with UL standards is required
.
Notes 2. Rod terminals cannot be used when compliance with UL standards is required.
Single-line, stranded-line: AWG24~14 (combined use of rod terminals possible for stranded-line applications)
Notes 1. AWG 24~18 can be used when compliance with UL standards is required.
Notes 2. Rod terminals cannot be used when compliance with UL standards is required.
Three phase 4-wire system: With VT
Three phase 3-wire system: Direct input, 2CT
qAuxiliary power supply:
100-240VAC or VDC
wFuse: 0.5A
*1 For low-voltage circuits,
secondary-side grounding of
instrument-use voltage/current
transformers is not required.
*2 Connection to NC terminal is
prohibited.
qAuxiliary power supply:
100-240VAC or VDC
wFuse: 0.5A
*1 For low-voltage circuits,
secondary-side grounding
of instrument-use
voltage/current
transformers is not
required.
*2 Connection to NC terminal
is prohibited.
Three phase 3-wire system: With VT, 3CT
20.7 86.2
106.9
91.6PANEL CUT
91.6PANEL CUT
91.6PANEL CUT
91.6PANEL CUT
95.8COVER
95.8COVER
Optional cover
106.9
86.2
20.7
20.7
86.2
106.9
95.8COVER
95.8COVER
91.6PANEL CUT
91.6PANEL CUT
wAttach the optional
unit to the main unit.
Insert hole Lever
w
T/R
T/R
T/R
T/R
MA
MB
SLD
SLD
er
MODBUS
®
RTU
Communication
k
K
L
C2
321
Load
0
q
(+)
(−)
C1
C1
C2
C3
C3
P1
P2
P3
PN
K
L
l
k
l
K
L
k
l
Protective
Earthing
MODBUS
®
RTU
Communication
T/R
T/R
T/R
T/R
MA
MB
SLD
SLD
er
w
C2
C1
C1
C2
C3
C3
P1
P2
P3
PN
u
v
u
v
u
v
U
V
U
V
U
V
Protective
Earthing
MODBUS
®
RTU
Communication
k
321
Load
0
K
L
K
L
l
k
l
K
L
k
l
q
(+)
(−)
T/R
T/R
T/R
T/R
MA
MB
SLD
SLD
er
MODBUS
®
RTU
Communication
Protective
Earthing
MODBUS
®
RTU
Communication
w
k
K
L
C2
321
Load
q
(+)
(−)
C1
C1
C2
C3
C3
P1
NC
P3
P2
l
K
L
k
l
U
V
u
v
u
v
U
V
K
L
l
k
w
T/R
T/R
T/R
T/R
MA
MB
SLD
SLD
er
Protective
Earthing
MODBUS
®
RTU
Communication
C2
C1
C1
C2
C3
C3
P1
NC
P3
P2
k
K
L
321
Load
l
K
L
k
l
q
(+)
(−)
External Dimensions/Installation/Connections
To prevent damage to the panel and screws, do not fasten screws
too tightly.
Recommended torque for these products: 0.3~0.5N·m (approx. half
of standard torque)
Also, please tighten the upper and lower screws at the same time.
Main unit mounting screws: M3
25 26