Specifications
‡Operation (for ME96SSH-MB)
Automatic (Auto)
Manual (Hold)
RESET
RESET
RESET
»Display Change
»Maximum/Minimum Display Values
»Displaying Active energy/Reactive energy/Apparent energy
»
Bar Graph Display
»
Reset Maximum/Minimum Values
»Changing Phases
»Changing Upper/Lower Limits for Alarm Activation and Cancellation
When measurement values exceed the upper/lower limit values that have been set, an alarm activates and the screen begins to blink.
The blinking mark on the bar graph indicates the current upper/lower limit value settings.
Press the button to change to the maximum and minimum values
of the display screen. Press it again to return to the current value display screen.
Press the button for 2s to reset the maximum/minimum values of
the measurement items displayed. The maximum/minimum values will
become the current values.
Press the and buttons simultaneously for 2s to reset all
maximum/minimum values. The maximum/minimum values will become the current values.
»
Reset Active energy/Reactive energy/Apparent energy
Press the , and buttons simultaneously for 2s to reset all of the following together:
active energy/reactive energy/apparent energy (this operation only works on the current value display screen).
<Screen 1 of 4>
Upper: Current
Middle: Power
Lower: Voltage
<Screen 2 of 4>
Upper: Current
Middle: Power
Lower: Power factor
<Screen 3 of 4>
Upper: Current
Middle: Power factor
Lower: Voltage
Average current
Power (total)
Average voltage (interphase)
Current phase 1
Power phase 1
Voltage phase 1N
Current phase 2
Power phase 2
Voltage phase 2N
Current phase 3
Power phase 3
Voltage phase 3N
Current phase 3
Power phase 3
Voltage phase 31
Current phase 2
Power phase 2
Voltage phase 23
Current phase 1
Power phase 1
Voltage phase 12
Average current
Power (total)
Average voltage
(between lines)
<Screen 4 of 4>
Upper: Current
Middle: No display
Lower: N-phase current
Example of changing display (Three phase 4-wire system; display pattern: P01; no additional screens)
Three phase 4-wire system
Example of changing phases (Three phase 4-wire system)
DISPLAY DISPLAY DISPLAY
DISPLAY
Press , the current phase and the voltage phase switches over.
PHASE
PHASE
PHASE PHASE PHASE
PHASE PHASE
PHASEPHASE
Items measured can be displayed on the bar graph. By displaying one item by a bar graph and other three items by digital numbers
four elements can be displayed at once.
• Bar graph explanation
The or mark indicates that the measurement item is displayed on the bar graph.
• Select bar graph
Press the or button to select the measurement items to be displayed on the bar graph.
Change the unit (M, k, none) or increase the digits in the bottom display for power used/reactive power used/apparent power
used/time-based power used to check the lower/higher-order digits. Push the and buttons simultaneously for 2s to switch
between screens.
(clockwise) (anticlockwise)
(Upper)
V
AVG
(LN) V
AVG
(LL) A
AVG
∑W
(Middle)
(Lower)
Hz ∑PF ∑var
Example of bottom item
displayed in the bar graph
Example of power factor
displayed in the bar graph
MAX/MIN
RESET
RESET
* To display these screens,
it is necessary to change
the power used measurement
settings using set-up menu 3.
Active energy (Imported) Active energy (Exported)* Apparent energy
Reactive energy
(Imported,lag)
Reactive energy
(Imported,lead)*
Reactive energy
(Exported,lag)*
Reactive energy
(Exported,lead)*
Unit: M Bottom digits increased Unit: None Unit: k
Power used (receiving): Example of changing 012,345,678,901,234.567Wh
Press and
for 2s
SET
RESET PHASE
»
During Alarm Generation
Alarm condition: When a measured value exceeds the alarm value setting, the screen begins to flash and the alarm contact closes.
Alarm cancelled: When the alarm is cancelled, the screen stops flashing and the alarm contact opens.
»
Alarm Cancel
The alarm can be reset automatically or manually. The alarm recovery method varies according to the reset method setting.
»
Alarm delay Time
If an alarm delay time has been set, alarm notification begins only when the measurement value exceeds the upper/lower limit
alarm value for a period longer than the alarm delay time.
»Harmonic Display »Changing the Harmonic Degree Display
The harmonic effective value, distortion ratio and content
ratio can be displayed. To do so, first set the harmonic
display (set-up menu: 3.7).
Press the or button to change the harmonic degree.
<Example of total harmonic current display> <Example of 5th-deg harmonic voltage display>
Upper: Degree No.
Middle: Distortion (content) ratio
Lower: Effective value
Alarm reset method
Measurement value ≥ Upper limit alarm value
(or ≤ Lower limit alarm value)
Measurement value < Upper limit alarm value
(or > Lower limit alarm value)
Constantly on
Upper/Lower limit indicator
Constantly on
(Alarm on hold)(Alarm activated)
Closed
Alarm contact
Screen
Automatic
(Auto)
Manual
(Hold)
Screen
Alarm contact
Closed Closed Open
Open
(Alarm cancelled)
RESET
Digital value
Flashing
*
On
On
Unit
Flashing
Flashing
On
Phase
Flashing
*
Flashing
*
On
Alarm activated
Alarm on hold
Alarm cancelled
Alarm status
If the item that caused the alarm is displayed on
the screen, the digital value, unit (A, V, W, var,
PF, HZ, %, DM, THD) and phase (1, 2, 3, N) will
be displayed as shown in the table below. If the
item is not displayed on the screen, the screen will
not flash.
* Only flashes if the phase that caused the alarm is being displayed.
Previous
measurement
screen
Next
measurement
screen
Harmonic current
Voltage total phase 1
Voltage total phases 2, 3
Current 1
st
-degree phase 1
Current 1
st
-degree phases 2, 3
Current 31
st
-degree phase 1
Current 31
st
-degree phases 2, 3
Displayed in order: 3rd,
5th, 7th, 9th, 11th, 13th,
15th, 17th, 19th, 21st,
23rd, 25th, 27th, 29th
PHASE
N-phase harmonic current
Current total phase N
Current 1
st
-degree phase N
Current 31
st
-degree phase N
Displayed in order: 3rd,
5th, 7th, 9th, 11th, 13th,
15th, 17th, 19th, 21st,
23rd, 25th, 27th, 29th
Harmonic voltage
Voltage total phase 1N
Voltage total phases 2N, 3N
Voltage 1
st
-degree, phase 1N
Voltage 1
st
-degree, phases 2N, 3N
Voltage 31
st
-degree, phase N
Voltage 31
st
-degree, phases 2N, 3N
Displayed in order: 3rd,
5th, 7th, 9th, 11th, 13th,
15th, 17th, 19th, 21st,
23rd, 25th, 27th, 29th
PHASE
DISPLAY DISPLAY DISPLAY DISPLAY
Example of switching between changing current value
display and maximum/minimum value display screens
Current value display screen
Maximum/Minimum value
display screen
MAX/MIN
or will flash
or will flash or will flash
Operating Instructions
The alarm resets automatically when the measurement value returns to within the upper/lower limit set value.
The alarm setting changes to “on hold” even after the measurement value becomes returns to within the upper/lower limit value setting. Once the
value returns to within the upper/lower limit value set, perform the following alarm recovery operations.
(Note: Alarm recovery operations cannot be carried out from the maximum/minimum value display screen or contact input screen.)
<To select item and cancel alarm>
When the item that caused the alarm is displayed, press the button to deactivate the alarm.
For items with phases such as current and voltage, it is necessary to
press the button for each phase to cancel the alarm.
<To cancel alarms for all items>
To cancel alarms for all items at once (batch), press the button for 2s when in operating mode.
RMS
○
○
○
Distortion
(content) ratio
○
―
○
RMS
○
○
○
Distortion
(content) ratio
―
―
―
RMS
○
○
○
Distortion
(content) ratio
○
―
○
Harmonic total
1st (fundamental)
3rd, 5th, 7th, 9th,
11th, 13th, 15th,
17th, 19th, 21st,
23rd, 25th, 27th,
29th ane 31st
N-phase harmonic current
Harmonic voltageHarmonic current
Degree
DISPLAY
Press , the measurement display switches over.
19 20