Specifications

Operating Instructions
Imported Exported
Lag Lead Lag Lead
Reactive energy
used measurement
method
2 Quadrants Measurement
4 Quadrants Measurement
Combinations
(set value)
I
II
III
IV
Display combinations
Wh Varh
Imported Exported
CT primary current value (value set for set-up menu 1.4.1 primary current setting )
A
Demand A
V
W
var
PF
SP. (special primary current value)
Output item
Setting range
−0.5~1~0.5 −0~1~0
+10 steps (approx. 250%)
±0 steps (100%: standard max. scale value)
−18 steps (approx. 20%)
+3 steps (approx. 120%)
±0 steps (100%: instrument rating)
−18 steps (approx. 20%)
oFF
(no limit)
on
(limit)
Setting Explanation
Output to +5% of upper limit and -5% of
lower limit (with respect to span value)
Output to +1% of upper limit and -1% of
lower limit (with respect to span value)
Note: Skip this setting when the analog output of all channel output items is set to “non.”
A
Demand A
W
Output item
Setting range
Positive-only Positive/Negative
+3 steps (approx. 120%)
±0 steps (100%: instrument rating)
−10 steps (approx. 40%)
ePower scale
DISPLAY
SET
Set-up menu
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
SET
eSet the maximum power/rolling demand scale value on the bar graph, and select positive-only scale
or positive/negative scale (rolling demand is only for ME96SSH-MB).
(1) Maximum scale value
(2) Positive-only or Positive/Negative
rSet the maximum reactive power scale value on the bar graph (ME96SSH-MB, ME96SSR-MB only).
The setting procedure is the same as that described in
ePower unit (1) Max. scale value.
The reactive power scale can only be positive/negative.
tSet the power factor scale on the bar graph.
−0.5~1~0.5 −0~1~0
ySet display combinations of receiving/transmitting, lag/lead, power
used/reactive power used and the measurement method for reactive
power used (ME96SSH-MB, ME96SSR-MB only).
Combinations I, II Suitable for measuring reactive power in facilities not equipped with in-house generators, and generally for capacitor loads
where the power factor is close to zero.
Combinations III, IV Suitable for measurements in facilities equipped with in-house generators.
uSelect with or without harmonic display (ME96SSH-MB, ME96SSR-MB only).
oFF on
(without) (with)
When the display is set to “on,” the harmonic value measured will be
displayed on an additional screen.
Select another set-up menu or end set-up
Set-up menu
tAnalog output limit
Adjust settings to match set-up menu No. 6.
qSet the output items for “analog output CH1.”
Select the measured items to be output from the table below.
wSet the details for “analog output CH1.”
(The following settings can be made separately from the measurement items included in the display pattern.)
(1) If analog output is selected for current, demand current, voltage, power,
reactive power, power factor (set-up menu: 6.1.1)
(2) If analog output is selected for current, demand current, power
(set-up menu: 6.1.2)
eSet the output items for “analog output CH2~4.”
The setting procedure is the same as that of qAnalog output CH1 output items
.
rSet the details for “analog output CH2~4.”
The setting procedure is the same as that of wAnalog output CH1 detailed settings
.
tSet the upper limit for analog output (same for all channels)
Select another set-up menu or end set-up
+3 steps (approx. 120%)
±0 steps (100%: instrument rating)
−18 steps (approx. 20%)
Positive/NegativePositive-only
<Example display screens>
Combination I
: Imported : Exported : varh lead : varh lag
Combination II Combination III Combination IV
DISPLAY
SET
This screen will not
appear if the power is
not selected in the
display pattern.
This screen will not appear if
the reactive power is not
selected in the display
pattern.
Set-up menu
uHarmonic display
y
Measure power consumption
tPower factor scale
rReactive power scale
Set-up menu 6: Analog output setting (ME96SSH-MB, ME96SSR-MB only)
This menu will not appear if ME-4210-SS96 (optional) is not installed.
non
A
1
A
2
A
3
A
N
A
AVG
(CH1)
Demand A
1
Demand A
2
Demand A
3
Demand A
N
Demand A
AVG
V
1N
V
2N
V
3N
V
AVG
(L-N) (CH2)
V
12
V
23
V
31
V
AVG
(L-L)
W
1
W
2
W
3
W
(CH3)
var
1
var
2
var
3
var
VA
1
VA
2
VA
3
VA
PF
1
PF
2
PF
3
PF
(CH4)
Hz
Harmonic A
1
Harmonic A
2
Harmonic A
3
Harmonic A
N
Harmonic V
1N
Harmonic V
2N
Harmonic V
3N
Three phase 4-wire
Three phase 4-wire
AVG: Average value, Σ: Total effective value
DISPLAY
SET
DISPLAY
SET
To next channel settings
qAnalog output CH1
output items
wAnalog output CH1
detailed settings
eAnalog output CH2~4
output items
rAnalog output CH2~4
detailed settings
20
4
12
mA
1-0.5 0.5
20
4
12
mA
1-0 0
0
20
4
mA
40kW
<Positive-only>
20
4
12
mA
0-
40kW 40kW
<Positive/Negative>
e(1)
r
t
u
q
w(1)
w(2)
t
To continue to set-up
Select the menu
number using the or
button.
To finish set-up
Press the or button
to display the End screen,
and then press the
button to save settings.
SET
To continue to set-up
Select the menu
number using the or
button.
To finish set-up
Press the or button
to display the End screen,
and then press the
button to save settings.
SET
Notes 1. The same measurement items can be set for all channels.
Notes 2. Measurement items not included in the selected display pattern can also be chosen.
Notes 3. Channels set to “non” will have minimum output (4mA). Additionally, set-up will proceed to the
next channel.
Notes 4. Underlined specifications are factory default settings of measurement items allocated to each
channel.
Notes 5. Harmonic current is output at the scale of 0~60% (with respect to rated value) of the total
effective value. Harmonic voltage is output at the scale of 0~20% of the total distortion ratio.
17 18