Specifications

Operating Instructions
<Continued from previous page>
Set-up menu 2: Communication settings (MODBUS
®
RTU, CC-Link communication settings)
(CC-Link communication only possible when ME-0040C-SS96 is installed to ME96SSH-MB, ME96SSR-MB)
eVT/Direct voltage
rCT current
DISPLAY
SET
DISPLAY
SET
tFrequency
DISPLAY
SET
yRolling demand time
limit
DISPLAY
SET
uDemand current time
limit
SET
Set-up menu
Set-up menu
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
wMODBUS
®
RTU
communication address
q
Select communication
system
(2) In the case of using with VT
<Secondary voltage settings>
  (a) Three phase 4-wire setting (phase voltage)
  (b) Three phase 3-wire (2CT, 3CT) or Single phase 2-wire setting (line voltage)
<Set primary voltage>
Can be set in 60~750,000V range (setting unit: V)
Under 100V: Top two digits settings
Over 100V: Top three digits settings
rSet CT
<Set secondary current>
1A       5A
<Set primary current>
Can be set in1.0~30,000.0A range (setting unit: A)
Under 10A: Top two digits settings
Over 10A: Top three digits settings
Set frequency
50Hz      60Hz
Notes1. Frequency scale on bar graph display will also change.
Notes2. Analog output scale will also change.
ySet the rolling demand interval time limit (ME96SSH-MB only)
(1) Interval time limit
(2) Sub-interval time limit
uSet the demand current time limit (ME96SSH-MB, ME96SSR-MB only)
Select another set-up menu or finish set-up
Adjust the set-up menu No. to “2”
qSelect CC-Link or MODBUS
®
RTU communication
CC: CC-Link communication
Mb. rtu: MODBUS
®
RTU communication
wSet MODBUS
®
RTU communication address
Possible address settings: 1~255
63.5V 100V 110V 115V 120V
100V 110V 220V
Factory default settings
Three phase 4-wire: 200V (phase voltage)
Three phase 3-wire; Single phase 2-wire: 10,000V (line voltage)
Factory default setting: 5.0A
Setting range
11560min
Setting interval
1min
Setting range
160min
Setting interval
1min
0 s
10 s
20 s
30 s
40 s
50 s
1 min
2 min
3 min
4 min
5 min
6 min
7 min
8 min
9 min
10 min
15 min
20 min
25 min
30 min
Set-up menu 3: Display settings (max. scale, active energy, harmonics, etc.)
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
Set-up menu
Set-up menu
oReset communication
qCurrent scale
wVoltage scale
eMODBUS
®
RTU
communication baud rate
rMODBUS
®
RTU
communication parity
tMODBUS
®
RTU
communication stop bit
yCC-Link communication
station number
uCC-Link communication
speed
iSet CC-Link
communication version
eSet the MODBUS
®
RTU communication baud rate.
rSet the MODBUS
®
RTU communication parity.
tSet the MODBUS
®
RTU communication stop bit.
Stop bit 1 Stop bit 2
ySet the CC-Link communication station number.
  Possible station number settings: 1~64
uSet the CC-Link communication speed.
iSet the CC-Link communication version.
Version 1.10 Version 2.00
oSet to “on” if changes have been made to the CC-Link settings
(if not set to “on,” changes will not be effective).
oFF      on
Select another set-up menu or end set-up
Change to set-up menu No. 3.
qSet the maximum current scale value on the bar graph
(1) Maximum current scale value
CT primary current value
S P.
(special primary current value)
(2) Maximum current scale value special setting
wSet the maximum voltage scale value on the bar graph
Maximum scale value
2400bps
4800bps
9600bps
19.2kbps
38.4kbps
156kbps
625bps
2.5Mbps
5Mbps
10Mbps
non
odd
evenEVEn
+3 steps (approx. 120%)
±0 steps (100%: instrument rating)
-10 steps (approx. 40%)
+10 steps (approx. 250%)
±0 steps (100%: instrument rating)
-18 steps (approx. 20%)
To continue to set-up
Select the menu No.
using the or button.
To finish set-up
Press the or button
to display the End screen,
then press the button
to save the settings.
SET
If ME-0040C-SS96 (optional) is not installed, this
screen will not appear. In addition, when CC-Link
communication is selected, settings are
performed from y CC-Link station No.
This screen will not be displayed if CC-Link
communication is selected using
qCommunication system selection.
This screen will not
appear if the current is
not selected in the
display pattern.
To continue to set-up
Select the menu
number using the or
button.
To finish set-up
Press the or button
to display the End screen,
and then press the
button to save settings.
SET
This screen will not
appear if the voltage is
not selected in the
display pattern.
This screen will not appear if “CT
primary current value” is
selected.
w
u
y
t
r
e(2)
Set-up menu 1.4.1
primary current setting
Set value
e
r
t
y
u
i
o
q(1)
q(2)
w
q
Set-up menu 2 screens e~t will not be displayed if CC-Link communication is selected using qCommunication system selection
.
Set-up menu 2 screens y~o will not be displayed if ME-0040C-SS96 (optional) is not attached or if CC-Link communication is selected using
qCommunication system selection
.