Specifications

Specifications
Standards Compliance
Electromagnetic Compatibility
Emissions
Radiated Emission
EN61326-1/CISPR 11
FCC Part15 Subpart B Class A
Conducted Emission
EN61326-1/CISPR 11
FCC Part15 Subpart B Class A
Harmonics Measurement EN61000-3-2
Flicker Meter Measurement EN61000-3-3
Immunity
Electrostatic discharge Immunity EN61326-1/EN61000-4-2
Radio Frequency Electromagnetic field Immunity EN61326-1/EN61000-4-3
Electrical Fast Transient/Burst Immunity EN61326-1/EN61000-4-4
Surge Immunity EN61326-1/EN61000-4-5
Conducted Disturbances
Induced By Radio Frequency Fields Immunity EN61326-1/EN61000-4-6
Power Frequency Magnetic Field Immunity EN61326-1/EN61000-4-8
Voltage Dips and Short Interruptions EN61326-1/EN61000-4-11
Safety
Europe CE
as per EN61010-1
U.S. and Canada cRUus as per UL61010-1
IEC61010-1
Installation Category
Measuring Category
Pollution Degree 2
Notes Regarding MODBUS
®
RTU Communication
Item Specifications
Interface RS-485 2-wire half-duplex transmission
Protocol RTU mode
Transmission method Asynchronous
Connection type Multi-point bus
Baud rate 2,400/4,800/9,600/19,200/38,400bps
Data bit 8
Stop bit 1 or 2
Parity Odd, even, none
Address 1 to 255 (0:for broadcast mode)
Distance 1,200m (max)
Max. connectable units 31 units
Terminal Resistance 120
Ω
1/2W
Recommended Cable Shielded twisted-pair AWG24 to 14
Notes Regarding CC-Link Communication
Item Specifications
No. of occupied stations 1 Station Remote device station
CC-Link version CC-Link Ver 1.10/Ver 2.00
Baud rate 10Mbps/5Mbps/2.5Mbps/625kbps/156kbps
Transmission method Broadcast polling system
Synchronous method Frame synchronous system
Encoding method NRZI
Transmission path format Bus format (EIA RS485)
Transmission format HDLC
Error control system CRC (X
16
+ X
12
+ X
5
+ 1)
Number of connectable units 42 units (max, remote device station)
Remote station Number 1 to 64
For CC-Link connection cables, please use the dedicated cables.
For information regarding dedicated cables, please refer to the CC-Link Partner Product Catalog published by the CC-Link Partner Association or CC-Link
Partner Product Information on the CC-Link Partner Association website (http://www.cc-link.org).
Notes 1. Dedicated CC-Link cables compatible with Ver. 1.00 cannot be used in tandem with dedicated CC-Link high-performance cables compatible
with Ver. 1.00.
Notes 2. In the case of systems consisting of units compatible with Ver. 1.00, 1.10 or 2.00 used in tandem with Ver. 1.00 or 1.10 cables, Ver. 1.00
specifications will apply for the maximum total cable length and length of cables between stations.
Notes 3. For terminal resistance, be sure to use 110
Ω
±5% (1/2W product) when using dedicated CC-Link cables or 130
Ω
±5% (1/2W product) when
using dedicated CC-Link high-performance cables.
Option Specifications
Item Specification Optional Plug-in Module type
Analog output 4-20mA (0~600
Ω
) ME-4210-SS96
Pulse/Alarm output
No-voltage “a” contact Capacity: 35VDC,
0.1A
ME-4210-SS96
Digital input 19-30VDC 7mA or less ME-4210-SS96
ME-0040C-SS96
ME-0052-SS96
Digital output
No-voltage a contact Capacity: 35VDC, 0.2A
ME-0052-SS96
11 12