Specifications
409
FDEN-H
Model FDEN258HEN-S1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode.
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C – 7˚C 6˚C
ISO-T1, JIS B8616
Operation data
(3)
Item
Model
FDEN258H FDC258HEN3A
Nominal cooling capacity
(1)
W 5700
Nominal heating capacity
(1)
W 6100
Power source 1 Phase, 220/240V, 50Hz
Cooling input kW 2.04/2.15
Running current (Cooling) A 9.4/9.4
Power factor (Cooling) % 99/95
Heating input kW 1.94/2.09
Running current (Heating) A 9.1/9.2
Power factor (Heating) % 97/95
Inrush current (L.R.A) A 51
Noise level
(4)
dB(A) Hi: 44 Lo: 39 52
Exterior dimensions
mm 184 × 1260 × 650 845 × 880 × 340
Height × Width × Depth
Net weight kg 27 55
Refrigerant equipment
– RM5526GNE4 × 1
Compressor type & Q’ty
Motor kW – 1.9
Starting method – Line starting
Heat exchanger Louver fines & inner grooved tubing Slitted fines & bare tubing
Refrigerant control Capillary tube
Refrigerant R22
Quantity kg Holding charged
1.1 [Pre-charged up to the piping length of 5m]
Refrigerant oil r – 0.7 (BARREL FREEZE 32SAM)
Defrost control MC controlled de-icer
High pressure control High pressure switch
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 4 Propeller fan × 1
Motor W25 × 255 × 1
Starting method Line starting Line starting
Air flow (Standard) CMM Hi: 16 Lo: 10.5 56
Fresh air intake Unavailable –
Air filter, Q’ty Polypropylene net ×2 (washable) –
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W – 20 (Crank case heater)
Operation control
Operation switch Wireless remote control switch – (Indoor unit side)
Room temperature control Thermostat by electronics –
Safety equipment
(5)
Internal thermostat for fan motor. Internal thermostat for fan motor.
Frost protection thermostat. Abnormal discharge temperature protection
Installation data mm
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Refrigerant piping size (in)
Connecting method Flare piping
Drain hose (Connectable with VP20) –
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit. Wireless remote controller
Optional parts –
FDEN258HEN-S1