Specifications
416
FDEN-H
10.2.2 Range of usage & limitations
Item
Models
FDENP208, 258 type FDENP308~508 type
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
Refer to the selection chart
Max. 50 m
Max. 10 times/h
Max. 3 minutes
Min. 85% of rating
Rating ± 10%
Max. 30 m (Outdoor unit is higher)
Max. 15 m (Outdoor unit is lower)
Max. 30 m
Max. 20 m (Outdoor unit is higher)
Max. 15 m (Outdoor unit is lower)