Specifications

415
FDEN-H
Model FDENP508HES-S
Operation data
(3)
Item
Model
FDEN508H FDCP508HES3
Nominal cooling capacity
(1)
W 12500
Nominal heating capacity
(1)
W 14000
Power source 3 Phase, 380/415V 50Hz
Cooling input kW 5.36/5.43
Running current (Cooling) A 9.5/9.8
Power factor (Cooling) % 86/77
Heating input kW 5.24/5.31
Running current (Heating) A 9.4/9.7
Power factor (Heating) % 84/76
Inrush current (L.R.A) A 74
Noise level
(4)
dB(A) Hi:50 Lo:44 55
Exterior dimensions
mm 239 × 1470 × 650 1250 × 920 × 340
Height × Width × Depth
Net weight kg 40 107
Refrigerant equipment
GU-A5560HS41 × 1
Compressor type & Q’ty
Motor kW 3.75
Starting method Line starting
Heat exchanger Louver fins & inner grooved tubing Slitted fins & bare tubing
Refrigerant control Capillary tube
Refrigerant R407C
Quantity kg Holding charged
2.58 [Pre-charged up to the piping length of 5m ]
Refrigerant oil r 1.6 (MA32)
Defrost control MC controlled de-icer
High pressure control High pressure switch
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan × 4 Propeller fan × 2
Motor W 55 × 265 × 2
Starting method Line starting Line starting
Air flow (Standard) CMM Hi:28 Lo:20 110
Fresh air intake Unavailable
Air filter, Q’ty Polypropylene net ×3(washable)
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W 40 (Crank case heater)
Operation control
Operation switch Wireless remote control switch – (Indoor unit side)
Room temperature control Thermostat by electronics
Safety equipment Internal thermostat for fan motor. Internal thermostat for fan motor.
Frost protection thermostat. Thermistor for discharge temperature.
Installation data mm
Liquid line: φ9.52 (3/8) Gas line: φ19.05 (3/4)
Refrigerant piping size (in)
Connecting method Flare piping
Drain hose (Connectable with VP20)
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit. Wireless remote controller.
Optional parts
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz.
(4) Indicates the value at mild mode.
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
ISO-T1, JIS B8616
FDENP508HES-S