Specifications
-
5
-
Item
Model
SRK20CD-S SRC20CD-S
Cooling capacity
(1)
W 2050
Power source 1 Phase, 220/230/240V, 50Hz
Cooling input kW 0.63
Running current (Cooling) A 3.1/3.0/2.9
Inrush current A 18.9
COP Cooling: 3.21
Cooling
sound level Hi 34, Me 28, Lo 26 46
Noise level
Power level
dB
52 60
Exterior dimensions
Height × Width × Depth
mm
250 × 815 × 249 540 × 720 × 290
Color Cool white Stucco white
Net weight kg 9.0 32
Refrigerant equipment
Compressor type & Q’ty
– RM-B5077MNE4 (Rotary type) × 1
Motor kW – 0.65
Starting method – Line starting
Heat exchanger Louver fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Refrigerant
(3)
kg R410A 0.9 (Pre-Charged up to the piping length of 15m)
Refrigerant oil R 0.35 (MA68)
Deice control MC control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 14 12
Air flow (at High) (Cooling) CMM 7.5 26
Air filter, Q’ty Polypropylene net (washable) × 2 –
Shock & vibration absorber – Cushion rubber (for compressor)
Electric heater ––
Operation control
Operation switch
Wireless-Remote controller –
Room temperature control MC. Thermostat –
Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4″) Gas line: φ9.52 (3/8″)
Connecting method Flare connecting
Attached length of piping Liquid line: 0.4 m
Gas line : 0.33 m
–
Insulation Necessary (Both sides)
Drain hose Connectable
Power source cord 2.5 m (3 cores with Earth)
Size × Core number 1.5 mm
2
× 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Optional parts –
Notes (1) The data are measured at the following conditions.
Model SRK20CD-S (Indoor unit)
SRC20CD-S (Outdoor unit)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27ºC19ºC35ºC24ºC ISO-T1, JIS C9612
(2) The operation data are applied to the 220/230/240V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 15 m connecting piping.
(Purging is not required even in the short piping.)
Operation data
(1)
Refrigerant
piping
Compressor: Overheat protection, overcurrent protection, Serial signal error protection, Indoor fan mo-
tor error protection, Frost protection
The piping length is 7.5m.