Specifications

-
81
-
(4) Installation of indoor unit
(a) Hang the upper portion of the unit rear cover on the mounting board,
and then magnet on the lower unit portion will pull to fix the unit.
(b) Be sure not to leave any trap on the drain pipe.
Wall
Declining slope
Inverted slipe
Trap
Slighty push
Mounting
block
5.3 Installation of outdoor unit
(1) Installation of outdoor unit
(a) Make sure that sufficient space for installation and service is secured.
(b) Fix the leg sections of the unit on a firm base which will not play.
Attach cushion pads, etc. between the unit and the mounting fixtures not to transmit vibration to the building.
(c) Attach a drain elbow, etc. under the drain port of the bottom plate to guide drain water. (Drain elbow should not be used
where days when temperature drops below 0˚C continue for several days. Draining may be disturbed by frozen water.)
(d) When installing the unit at a higher place or where it could be toppled with strong winds, secure the unit firmly with founda-
tion bolts, wire, etc.
(2) Connection of indoor and outdoor connecting wiring
(a) Connect the wiring according to the number of the indoor terminal block. (Mis-wiring may cause the burning damage, and
make sure to connect correctly.)
(b) When an abnormality is indicated on the outdoor unit for the cooling only model, check the fuse on the outdoor unit. If the
fuse is burnt out, replace it with new one.
5.4 Refrigerant piping
(1) Preparation
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
Indoor unit side
Outdoor unit side
¡ Remove the flared nuts.
(on both liquid and gas sides)
¡ Remove the flared nuts.
(on both liquid and gas sides)
¡ Install the removed flared nuts to the pipes to be connected,
then flare the pipes.
Dimension A
Liquid side
(φ6.35): 9-9.5 dia
Gas side
(φ12.7): 16.2-17 dia
Press
Remove
Press
Remove
(Do not
turn)
Cooling only
type type
1 BROWN
2 BLUE
3 BLACK
4 GREEN
YELLOW
GREEN