Specifications

-
80
-
(3) Preparation of indoor unit
(a) Mounting of connecting wires
(i) Open the suction grille, then remove the lid.
(ii) Remove the wiring clamp.
(iii) Pass the connecting wire to terminal block from behind of indoor
unit.
(iv) Connect the connecting wire securely to the terminal block.
1 Connect the connection wire securely to the terminal block. If the
wire is not affixed completely, contact will be poor, and it is dan-
gerous as the terminal block may heat up and catch fire.
2 Take care not to confuse the terminal numbers for indoor and out-
door connections.
3 Affix the connection wire using the wiring clamp.
(v) Fix the connecting wire by wiring clamp.
(vi) Attach the lid.
(vii) Close the suction grille.
(b) Protective taping (Protect the cable with tape at the section where the cable passes through the hole opened on the wall.)
(c) Forming of pipe (Holding down the pipe at the root, change the pipe direction, extend it and adjust according to the
circumstance.)
Screw
Suction grille
Connecting wire
Wiring clamp
Terminal
block
Lid
[When the pipe is extended to left and taken out from the rear center]
Note (1) It is designed to collect moisture
accumulated on the rear face in the
drain pan. Be sure not to accommodate
the power cable, etc. above the chute.
¡ When arranging the pipe through a hole opened at the center, open the
knockout hole using nippers, etc.
(Drain pipe relocation procedure)
1. Remove the drain pipe. 2. Remove the drain cap. 3. Insert the drain cap. 4. Connect the drain pipe.
¡ Loosen the spring clamp and
securely insert the drain pipe.
Note: If it is inserted insufficiently,
water leakage could result.
Pipe accommodation space
¡ Loosen the spring clamp to
remove.
¡ Remove by hand or use
cutting pliers, etc.
¡ Securely insert the drain cap
removed in the step 2.
Note: If it is inserted insufficiently,
water leakage could result.
Chute
Wall
Cooling only
type type
1 BROWN
2 BLUE
3 BLACK
4 GREEN
YELLOW
GREEN
Use cables for interconnection wiring to avoid loosening of the wires.
CENELEC code for cables Required field cables.
H05 RNR3G1.5 (Example)
H Harmonized cable type
05 300/500 volts
R Natural-and/or synth, rubber wire insulation
N Polychloroprene rubber conductors insulation
R Stranded core
3or5 Number of conductors
G One conductor of the cable is the earth conductor
(yellow/green)
1.5 Section of copper wire (mm
2
)