Specifications

-
73
-
(4) AUTOMATIC operation
(a) Determination of operation mode
The blow operation of the indoor fan is carried out at the 1st speed for 20 seconds and the room temperature is checked to
determine the operation mode automatically. (When the unit is operated by the turn-on timer, the blow operation is not
carried out.)
(b) The temperature is checked once every 30 minutes after operation start. When the judgment is different from the previous
operation mode, the operation mode is transferred.
(c) When the unit is operated again within 30 minutes after the operation stop or the operation of the unit is changed to the
automatic operation during cooling, heating or dry operation, the unit is operated with the previous operation mode.
(d) Established temperature (operate by the established temperature button on remote controller).
(5) Comfort timer settings
Temperature is checked beginning 1 hour before the set time, and the power is turned on before the timer setting as necessary to
bring the temperature to the proper level by the set time.
Operation mode Room temperature thermistor (Th1)
Operating start time (amount of time
previous to set time that operation begins)
Over 40˚C 60 mins.
Cooling Over 35˚C 30 mins.
Over 30˚C 15 mins.
Notes (1) At 5 minutes before the set time of the turn-on timer, the operation is started regardless of the temperature of the room temperature thermister.
(2) When the dry or blow operation is selected, this function is not activated.
(However, when the automatic dry operation is selected, the function described in article (1) is operated.)
(6) Timer time setting
The turn-off timer and turn-on timer can be set for up to 12 hours in units of 1 hour.
(7) Night time turn off
Placing the timer to this setting changes the temperature setting of the indoor set button as follows:
Wireless remote control signal (Indication)
-6 -5 -4 -3 -2 -1 ±0+1+2+3+4+5+6
Cooling 20 21 22 23 24 25 26 27 28 29 30 31 32
Thermal dry 19 20 21 22 23 24 25 26 27 28 29 30 31
Temperature
setting
(8) Temperature adjustment
a) Temperature adjustment setting may be set between 18 and 30˚C.
b) The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
Cooling
c) During the continuous mode, the compressor runs continuously in cooling. For thermal dry, please refer to page 79.
Compressor
outdoor fan
Set temp.
Room temp.
Cooling, thermaldry
Start
Timer operation
(time)
Temperature
setting (˚C)
21ºC Room temperature<26ºC 26ºC Room temperature
Operation mode Dry Cooling