Specifications
-
48
-
(14) Self diagnosis function
When something abnormal happens on the outdoor unit, indoor unit fan motor and each thermistor (heat exchanger, room tempera-
ture, ) it will be indicated by flashing lamps.
(a) Abnormality of outdoor unit: When the indoor heat exchanger temperature does not fall to 25ºC or below for 40 minutes
(12 type : 20 minutes) after 5 minutes have elapsed since the compressor operation start,
the abnormality stop occurs. (The timer lamp flashes 5 times.)
(b) Abnormality of indoor fan motor: The indoor fan motor revolves at a rate under 300 rpm for 30 seconds or longer, the
RUN lamp will flash.
(c) Abnormality of heat exchanger thermistor: RUN lamp will flashing when the input temperature of the heat exchanger
thermistor measures less than –20ºC for more than 3 seconds with the
airconditioner “OFF”. (will not flashing during operation)
(d) Abnormality room temperature thermistor: RUN lamp will flashing when the input temperature of the room tem-
perature thermistor measures less than –20ºC for more than 3 seconds
with the airconditioner “OFF”. (will not flashing during operation)
Note (1) If the above abnormalities happen concurrently, the lamp will flashing in the order of item number (a) through (d) above.
(13) Three-Minute Forced Operation
When the compressor begins operating the thermal operation is not effective for 3 minutes, so operation continues as is in the
operation mode. (After 3 minutes has passed the thermal operation is effective.)
However, stopping the compressor via a stop signal or protection control has priority.