Specifications

-
46
-
(b) Fan speed knob: AUTO
The indoor fan is automatically controlled in accordance with the difference between the room temperature (detected
by the room temperature thermistor) and the thermostat setting as shown below.
Mode
Cooling Fan
18~30˚C
Thermostat setting point Thermostat setting point
Continuous Speed 4 Speed 3
Mode
COOL FAN
Fan speed knob
AUTO See below
LOW Speed 1 (Speed 1) Speed 1 (Speed 1)
MED Speed 2 (Speed 2) Speed 2 (Speed 2)
HIGH Speed 3 (Speed 4) Speed 3 (Speed 3)
Notes (1) Please refer to page 46 regarding dry operation.
(2) Figure in ( ) shows the case that the set temperature is continuing.
(9) Fan control
(a) Fan speed change
Set-
ting temp
Note (1) Please refer to page 46 regarding dry operation.
Note (1) Thermostat operation is performed in A, B Block. When compressor and indoor fan stop by thermostat operation within 12 minutes from start, temperature
check is performed by operating indoor fan at speed 1 for 20 seconds before finishing 12 minutes and allowing decision of next operation block.
D Block C Block B Block A Block
(10) DRY operation
(a) Choose the appropriate operation block area by the difference between room temperature and thermo-
stat setting temperature as shown below.
¡Operation block area
–2 0 +3
Room temp. – Setting temp.(deg)
(b) Start up operation
Speed 1
Speed 3
Speed 4
Speed 2
Speed 2
Speed 3
Speed 1
ON
OFF
OFF
0
3
6
912
ON
OFF
OFF
0
12
Compressor
and
outdoor fan
Set fan speed
Indoor fan
Start
Temperature check
Start
Temperature check
Compressor
and
outdoor fan
Set fan speed
Indoor fan
Operation block decision
C.D Block
A.B Block
minutes
minutes
Speed 1
20
seconds