Specifications

70
SRK-H
Note (1) The unit performs heating to the set time after 2.0 hours in the night time as shown right.
(d) Temperature adjustment
1) Temperature adjustment setting may be set between 18 and 30˚C.
2) The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
Timer operation
(time)
3) During the continuous mode, the compressor runs continuously in both cooling and heating. For thermal dry, please refer to
page 73.
Compressor
outdoor fan
Set temp. -Room temp.
(deg)
Start
Timer operation
(time)
Temperature
setting (˚C)
Start
Temperature
setting (˚C)
Room temp.
Set temp.
Compressor
outdoor fan
Room temp.
Heating
Cooling, thermaldry
HeatingCooling
Set temp.
(a) Comfort timer settings
Temperature is checked beginning 1 hour before the set time, and the power is turned on before the timer setting as necessary to
bring the temperature to the proper level by the set time.
Operation mode Room temperature sensor (Th1)
Operating start time (amount of time
previous to set time that operation begins)
Under 5˚C 60 mins.
Heating
Under 10˚C 30 mins.
Under 15˚C 15 mins.
Over 15˚C 5 mins.
Over 40˚C 60 mins.
Cooling
Over 35˚C 30 mins.
Over 30˚C 15 mins.
Under 30˚C 5 mins.
(b) Timer time setting
The turn-off timer and turn-on timer can be set for up to 24 (32, 40: 12) hours in units of 1 hour.
(c) Night time turn off
Placing the timer to this setting changes the temperature setting of the indoor set button as follows:
OFF
ON
Compres-
sor
outdoor fan