UNIT 18K & 24K, 230 Volts (Cont.)
Malfunction
Indoor Unit Display
Outdoor unit display
(LED’s have 3 modes)
OFF, ON, Flash
Operation Status Malfunction
Error
Code
Display
Indicator Display
(LED Flash 0.5sON/0.5sOFF
Running
LED
Cooling
LED
Heating_
LED
D40
/D5
D41
/D6
D42/
D16
D43/
D30
Outdoor unit error U9
Cooling: compressor
will stop, indoor fan
runs, heating all stop
Replace outdoor
board AP1
Indoor freeze protection FH
Operation normal,
compressor speed
reduced
Indoor unit return air
blocked or fan speed
is too low
Fan module protection L3
Cooling: outdoor fan
motor and
compressor stop;
indoor fan runs.
Heating all stop
1. Outdoor fan
terminals loose,
correct problem
2. Motor damaged,
replace motor
3. Fan motor module
on mainboard is
damaged; replace
mainboard AP1
Remark
1. Error codes only can be seen in the type which has the temperature display PCB. Some types do not have this function and
have only the LED’s on the outdoor PCB.
2. If there is normal communication between the Indoor and Outdoor unit the green LED will be on.