Instruction manual
INSTALLATION INSTRUCTIONS R−410A Ductless Split System: DLF4(A/H), DLC4(A/H)
18 421 01 9220 00
UNIT 18K & 24K, 230 Volts (Cont.)
Malfunction
Indoor Unit Display
Outdoor unit display
(LED’s have 3 modes)
OFF, ON, Flash
Operation Status Malfunction
Error
Code
Display
Indicator Display
(LED Flash 0.5s−ON/0.5s−OFF
Running
LED
Cooling
LED
Heating_
LED
D40
/D5
D41
/D6
D42/
D16
D43/
D30
PFC protection HC
3s off flash
6 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Refer to service
manual
Compressor speed
reduction
H7
3s off flash
7 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Refer to service
manual
Heating, high temp H0
3s off flash
10 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Refer to service
manual
Start−up failure LC
3s off flash
11 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Refer to service
manual
Compressor current
circuit malfunction
U1
3s off flash
13 times
Replace outdoor
board AP1
EEPROM malfunction EE
3s off flash
15 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Replace outdoor
board AP1
Capacity charge
malfunction
PU
3s off flash
17 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Refer to capacitor
charging service
manual
Module Sensor circuit
malfunction
P7
3s off flash
18 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Replace the outdoor
boar AP1
Module over temp
protection
P8
3s off flash
19 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Check the IPM heat
sink or replace
outdoor board AP1
Low DC bus voltage U3
3s off flash
20 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
Supply voltage is not
stable
Low DC bus voltage
protection
PL
3s off flash
21 times
Cooling,
dehumidifying;
compressor stops,
indoor fan motor
runs, heating all stop.
1. Check supply
voltage, if voltage
lower than 150VAC,
restart the unit when
the power supply is
normal.
2. Check reactor L
connection
IPM temp high
limit/decrease
compressor run speed
EU
Operation normal,
compressor speed
reduced
Check the IPM heat
sink or replace
outdoor board AP1
Four−way valve
malfunction
U7
In heating mode, all
stop
1. Supply voltage is
lower than AC175vV
2. 4−way valve
terminal loose/broken
3. 4−way valve
damaged