Specifications

CHAPTER 6 CONNECTION OF REMOTE I/O UNIT
6.13 Connection of FCUA-DX14 Unit and Analog Input/Output Signal
89
6.13 Connection of FCUA-DX14 Unit and Analog Input/Output Signal
For the analog input/output signal, the R031 cable is connected to "AI0". Up to four input points and one
output point of the analog input/output signal can be connected. When manufacturing the R031, use the
connector set CS000 (optional, with two ends). (Refer to the Appendix 2.11. Cable manufacturing
drawing.)
AIO
FCUA-DX14
R031 cable
1
10
11
20
Pin No.
DAC
220
R
R
150
ADC
A10
A11
A12
A13
A0
150
150
150
2
12
3
13
1
11
5
15
7
GND
GND
GND
GND
Connector pin No.
Input
Output
FCUA-DX14
Incorrect connections could damage the device, so always connect the cable to the
designated connector.
Do not connect or disconnect the connection cables between each unit while the power is
ON.
CAUTION
Input/output circuit