CHAPTER 5 CONNECTION OF I/O INTERFACE
5.4 Scan I/O
72
(6) Digital output (CF33)
The HR347 output circuit is a sink type (sink output), and the HR357 output circuit is a source type
(source output).
+24V
RA
R
PL
GND
HR357
GND
+24V
HR347
RA
R
PL
GND
Sink type
Source type
Control
circuit
Control
circuit
(Machine side) (Machine side)
CF33 CF33
Output conditions
Insulation method Non-insulation
Rated load voltage DC+24V
Max. output current 60mA/point
Saturation voltage 1.6V (standard)
Output delay time
40µs
Do not apply voltages other than those indicated in this manual on the connector. Doing
so may lead to destruction or damage.
∗ When using an inductive load such as relays, always connect a diode (withstand voltage
100V or more, 100mA or more) in parallel to the load as a noise measure.
∗ When using a capacitive load such as a lamp, always connect a protective resistor
(R=150Ω) serially to the load to suppress rush currents. (Make sure that the current,
including the instantaneous current, is less than the above tolerable current.)
CAUTION