Specifications

APPENDIX 3 EMC INSTALLATION GUIDELINES
4. Panel Structure
122
4.2 Measures for Door
(1) Use metal for all members configuring the door.
(2) When joining the door, use a gasket to lower the impedance of the contacting sections, or use a
structure with a large contact area as shown below.
a) Use of gasket b) Large contact area
EMI gasket
Control panel
Contact area
Control panel
Door
Door
The EMI gasket or conductive packing must contact a uniform and correct position of the metal
surface.
When not using a gasket, ground the control panel grounding with a grounding wire to lower the
door's impedance.
Using screws to fix the plates that have been painted (attachment of packing) is the same as
an insulated state. Peel the paint and fix the screws.
CAUTION
Cross-section drawing