Specifications
169
(2) Indication of self diagnosis
Indoor unit indicator
RUN lamp
1 time flash
2 time flash
5 time flash
6 time flash
Keeps flashing
Keeps flashing
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
Comes on
1 time flash
2 time flash
1 time flash
2 time flash
2 time flash
3 time flash
4 time flash
5 time flash
6 time flash
Stays off
Stays off
Stays off
Stays off
Stays off
Stays off
1 time flash
2 time flash
3 time flash
4 time flash
5 time flash
6 time flash 
(3)
Indoor heat 
exchanger
thermistor error
TIMER lamp
Outdoor unit indicator
(LED5)
Description
of trouble
Cause Conditions of flashing
On for 4 seconds 
and off for 4 
seconds
Outdoor heat
exchanger gas
pipe thermistor
error
●
 Broken heat exchanger 
thermistor wire
●
 Connector poor connection
●
 Compressor locking
●
 Open phase on compressor 
output
●
 Shortcircuit on power 
transformer
●
 Broken power transformer
●
 Broken compressor wire 
●
 Compressor blockage
When heat exchanger thermistor temperature 
of –20 °C or under continued for more than 
3 seconds while operation is stopped. (This 
is not displayed during operation.) 
When room temperature thermistor tempera-
ture of –20 °C or under continued for more 
than 3 seconds while operation is stopped. 
(This is not displayed during operation.)
When air conditioner is operating and indoor 
fan motor is turned ON, indoor fan motor 
speed of 400 rpm or under continued for 
more than 30 seconds. (Air conditioner 
stops.)
When outdoor temperature sensor tempera-
ture of –40 °C or under continued for more 
than 3 seconds while operation is stopped. 
(This is not displayed during operation.)
When heat exchanger entrance thermistor 
temperature of –50 °C or under continued 
for more than 3 seconds while operation is 
stopped. (This is not displayed during opera-
tion.)
When the input current of 1 A or less is detect-
ed for 30 continuous seconds or more. (Com-
pressor stops.)
When converter output current which 
exceeds setting value is detected. 
(Compressor stops.)
When the input current value exceeds the set 
value. (Compressor stops)
When the discharge pipe thermistor tempera-
ture measures an interrupted signal (less than 
7 °C) of 10 seconds or more.
When power transistor temperature exceeds 
setting value.
(Compressor Stops.)
When discharge pipe thermistor value 
exceeds setting value.
(Compressor Stops.)
If serial signal cannot be sent or received for 
1 minute and 55 seconds continuously.
●
 Defective power supply
●
 Broken signal wire
●
 Defective indoor/outdoor 
unit circuit boads
Float switch motion 
●
 Broken room temperature 
thermistor wire
●
 Connector poor connection
●
 Drain at reverse gradient
●
 Float switch defective
●
 Defective fan motor
●
 Connector poor connection
●
 Broken outdoor thermistor 
wire
●
 Poor connector connection
●
 Broken heat exchanger gas 
pipe thermistor wire
●
 Poor connector connection
●
 Broken discharge pipe 
thermistor wire
●
 Connector poor connection
●
 Overload operation
●
 Overcharge
●
 Cooling problem
●
 Gas shortage
●
 Defective discharge pipe 
thermistor
Room temperature
thermistor error
Drain
abnormality 
(1)
Indoor fan
motor error 
(2)
Outdoor
temperature
thermistor error
Current cut
Trouble of
outdoor unit
Discharge pipe
thermistor error
Over current
Over heat of
power transistor
Over heat of
compressor
Error of signal
transmission
Notes (1) Ceiling recessed type only
(2) Wall mounted type only
(3) LED 5 will go out when even one unit is operating properly or there is an abnormality with the outdoor unit power supply. It will also go out during
normal operation.