Service manual

24
11-2-2. Wired remote controller
11-2-3. Failure mode table (Wireless remote controller/Wired remote controller)
Turn on the power.
Press the [CHECK] button twice.
Set refrigerant address with [TEMP] button
if system control is used.
Press the [ON/OFF] button to stop the self-check.
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
CHECK button
Refrigerant address
TEMP. button
IC: Indoor unit
OC: Outdoor unit
Check code
[Output pattern A] Errors detected by indoor unit
Beeper sounds/OPERATION INDICATOR
lamp blinks
Wireless remote controller
Check code
Wired remote controller
Symptom Remark
(Number of times)
1
P1
Intake sensor error
2
P2
P9
Pipe (TH2) sensor error
Pipe (TH5) sensor error
3
E6,E7
Indoor/outdoor unit communication error
4
P4
Drain sensor error/Float switch connector open
5
P5
Drain pump error
6
P6
Freezing/Overheating protection operation
7
EE
Communication error between indoor and outdoor units
8
P8
Pipe temperature error
9
E4, E5
Remote controller signal receiving error
10
11
12
Fb
Indoor unit control system error (memory error, etc.)
E1, E2
Remote controller control board error
E0, E3
Remote controller transmission error
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Check code
Symptom Remark
1E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
2UP Compressor overcurrent interruption
3U3,U4 Open/short of outdoor unit thermistors
4UF Compressor overcurrent interruption (When compressor locked)
5U2 Abnormal high discharging temperature/insufficient refrigerant
6U1,Ud Abnormal high pressure (63H operated)/Overheating protection operation
7U5 Abnormal temperature of heat sink
8U8 Outdoor unit fan protection stop
9U6 Compressor overcurrent interruption/Abnormal of power module
10U7 Abnormality of super heat due to low discharge temperature
11
U9,UH
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
12
13
14Others Other errors
If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp
does not come on,
there are no error records.
If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal
was received, the specified refrigerant address is incorrect.
For details, check the LED display
of the outdoor controller board.
On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
On wired remote controller
Check code displayed in the LCD.
Beeper sounds/OPERATION INDICATOR
lamp blinks
Wireless remote controller
Wired remote controller
(Number of times)
OCH472A