b.- If NO is selected, remember that the binary file with the project needs to
be generated before the IntesisBox
®
starts to work as expected.
3.- Once in the configuration window again, click on exit. Configuration file is ready
to be sent to the IntesisBox
®
device.
4.- Press the Send File button to send the binary file to the IntesisBox
®
device. The
process of file transmission can be monitored in the IntesisBox
®
Communication
Console window. IntesisBox will reboot automatically once the new configuration is
loaded.
After any configuration change, do not forget to send the configuration file
to the IntesisBox® using button Send File.
Signals viewer 4.4
Once the gateway is running with the correct configuration, to supervise the status of the
configured signals, press the Signals button on the menu bar (see Figure 4.1). The Signals
Viewer window will open (see Figure 4.6).
This window shows all signals active within the gateway with its main configuration
parameters and its real time value
1
in the Value column.
Figure 4.6 LinkBoxMB Signals Viewer
The signals viewer can be used even though only one system is connected to the
IntesisBox
®
, Modbus or Mitsubishi Heavy Industries AC. Therefore, it becomes convenient
for supervision and testing the system.
1
In case you connect to the IntesisBox
®
when it’s been running for a certain time, you should press the Refresh
button to get updated values. After pressing Refresh, all signal values will keep continuously updated until the
connection is closed.