Next, there is an explanation for each of the configuration parameters in each mode.
Modbus interface configuration parameters:
Figure 4.3 Modbus interface configuration
1. Select the type of Modbus communication to use (TCP, RTU or both).
If Modbus TCP is selected, then:
2. IP IntesisBox: Enter the IP address for IntesisBox
®
.
3. Net Mask: Enter the IP netmask for IntesisBox
®
.
4. Gateway: Enter the default gateway address for IntesisBox
®
; leave it blank if no
router is needed.
5. Port: Enter the TCP port to use (default for Modbus TCP is 502).
6. Timeout Keep Alive: Enter the time (expressed in seconds) that IntesisBox
®
will
wait, upon no TCP activity, to send a Keep Alive packet. Enter 0 if you don’t want
IntesisBox
®
to send any Keep Alive packet (default 30 seconds).
If Modbus RTU is selected, then:
7. Connection: Select the physical media (EIA232 or EIA485)
1
.
8. Baud rate: Enter the baud rate of the serial communication.
9. Parity: Enter the byte parity of the serial communication.
10. Slave: Introduce the Slave number for the Modbus interface.
1
In the LinkboxMB this connection is labeled as RS232 and RS485 respectively.