In case there is no communication with the IntesisBox
®
, check that the Modbus TCP devices
are operative and reachable from the network connection used by IntesisBox
®
. You can also
check that the IntesisBox
®
Ethernet interface is sending Pings to its IP address using a PC
connected to the same Ethernet network.
3.2.3 Connect to PC (LinkBoxMB)
Connect the IntesisBox
®
device to the PC serial port using the serial cable provided. One
end should be connected to the Console EIA232 port of the IntesisBox
®
device (see Figure
3.1) and the other end to the PC serial port.
IntesisBox
(DB9 F)
EIA232
Serial
Console
PC Connection (LinkBoxMB)
PC
(DB9 M)
Cable
(DB9 M)
EIA232
(Straight)
Cable
(DB9 F)
TX
2
2
RX
RX
3
3
TX
GND
5
5
GND
Table 3.6 EIA232 serial connection pin assign
Power Device 3.3
To power up the device, what you need is to plug properly the Power Supply connector to
the IntesisBox
®
device using a proper cable and connecting one end to the power supply
connector (see Figure 3.2) and the other end to the power line. After that, just press the
power supply On/Off button to turn it on.