Specifications

-
9
-
’10 • SC-T-154
(10) Control switch selection
It is possible to change the setting as follows by settings of the PCB switches SW1 to SW10, J1, J2, and J3 on the central
control.Please change the control on site as necessary. It is recommended to change the setting by using a precise driver.
(a) Switch
(*1) Switching is needed if the connection is previous Super Link.
Actual type of network connection (New or previous Super Link) depends on the models of indoor units and outdoor units, etc. Please contact the agency or
the Sales representative.
(*2) When J1 is disconnected, the Center/Remote does not be set from this central control. Please disconnect if multiple central controls are installed and another
main central control exists.
When J1 is disconnected data is sent for the blower only during demand input (nothing) is performed when SW6 is off) and for stop only during emergency
stop input
J1
Function
When disconnected
Short circuit (default)
Setting not possible
(Including during
external input.)
Setting
possible
SW1 to 10
(Left-OFF, Right-ON)
J1
J2
J3
Center/Remote setting
(*2)
(Including the allowed/prohibited settings
of each remote control function)
1
2
3
4
5
6
7
8
9
10
SW No.
SW
Description
(Keep at OFF)
Operation after
emergency stop cancel
The units
have stopped
Return to the
original status
4th fan speed set
Error history display
Sending of data during demand input
Filter sign display on/off
Automatic mode display
New/Prev. Super Link
(*1)
Power failure
compensation function
OFF
Month. Day Time
See table
at right
Auto mode cannot be set
No display
Previous
Center
ON
See table
at right
Auto mode can be set
setting not possible
setting possible
Display
New
Center & Fan
Time Month. Day
ON
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
Default
1
2
3
4
5
6
7
8
9
10
SW-1 SW-2
ON
ON
OFF
OFF
ON
OFF
ON
OFF
Sending of operation status before power failure
(Do not make this setting.)
No data is sent when power comes back on
Function
Sending of program settings when power comes back on
(The operation status before the power failure is sent if
there is no program when power comes back on.)
Power failure compensation function selector
(b) Jumper wires
(11) Setting the control target units
Make the settings for the units to be controlled by the central control.
For the setting procedure, see the user’s manual attached to the central contrl.
At shipping, none of the units are set as target units for control, and so the units to be controlled by this
central control must be set as control target units.
Three types of settings are available.
Units are selected as control targets for central control and controlled as a group
/
Group setting
Units are selected as control targets for central control but not grouped
/
Individual setting
Units are not selected as control targets for central control
/
Not target units for control
(or units will be controlled by another central control)
Be sure to set the current time. This is needed for the program settings and error history display.
Turn on the power and press the three buttons (MENU, RESET, GROUP No. 10) at once more than five second, that can
initialize the setting contents.
c
Group control when using multiple units
This central control can control up to 64 target units (up to 48 units when using the previous Super Link setting). Multiple
central controls must be installed to control 65 or more air conditioner units.
When connecting multiple central controls on a single network, any group settings can be made for each central control.
1 2 3 4 5 6 7 8 9 10 45 46 47 48
a-Gr1 a-Gr2
b-Gr1
c-Gr1
c-Gr16
a-Gr16
SC-SL2NA-E SC-SL2NA-E SC-SL2NA-E
a b c