Installation manual
-
4
-
7Remove the upper case of the interface.
• Take out the 2 screws in the interface case.
8Install the indoor unit’s connection cable in the interface.
• Connect the connector of the indoor unit connection cable to the
connector on the interface’s circuit board.
9Fasten the indoor unit connection cable using clamp.
• Cable can be brought in from the top or from the back.
• Use side cutters, etc. to cut out the thin knockouts used to run wires into the case.
0
Connect the indoor unit’s connection cable to the control board in the indoor unit.
• Connect the indoor unit connection cables’ connector securely to the
indoor unit’s control board.
• Use the clamp provided as an accessory to fasten the connection cable,
fastening it securely to the control box.
•
Read the installation manual for the indoor unit concerning connections inside the indoor unit.
Connecting the interface and the indoor unit
7Remove
the upper
case
8Install the indoor unit
connection cable
9Fasten with the clamp
Names of each part of the interface unit
Indoor unit connection terminal
Wired remote control*
terminal block
CNT terminal
Clamp for fastening the wired*
remote control connection cable
ROM terminal
Wiring inlet
(top or back)
DIP switch (SW2)
DIP switch (SW3)
Address setting rotary switch (SW1)
Super link adapter (SC-ADN-E) terminal block*
Clamp for fastening the super link adapter *
(SC-ADN-E) connection cable
* Either the super link adapter (SC-ADN-E) cable or the wired remote control connection cable can be connected.
Interface board
Clamp for fastening indoor
unit connection cable