Specifications
-
3
-
’13 • SC-T-192
2. OPERATION AND SETTING
Operation and setting is implemented in group or in a batch for the maximum 128 groups (144 for previous SL).
Notes (1) Don’t use the auto mode on any indoor unit other than those connected to the simultaneous heating & cooling 3-pipe system or single.
(2) Do not set the set point at 0.5˚C intervals in case this product is used with RCD type wired remote control.
It would cause malfunction of the wired remote control. Please make sure to set at 1˚C intervals.
(3) This function can be applied to the indoor units, which are the model KXE4 or later, SC-ADN-E or later and to the remote control, which is the model
RC-E1 or later.
(For models earlier than the above-mentioned, the function becomes invalid because the indoor unit and remote control cannot receive the instruction
even though the setting can be displayed.)
Since setting is overwritten in SL4-AE (SL4-BE) even if setting is done from the remote control, set using SL4-AE (SL4-BE).
However, “ALL Lock” and “ALL Unlock” can be set for old indoor models. (Same to “Center” or “Center & Remote”)
(4) This function becomes valid only in combination with the indoor unit model KXE6D or newer and SC-ADNA-E or newer.
For the previous indoor units, it is not possible to set the 4th fan mode, but other setting is possible as before.
4th fan speed setting is “invalid” by factory default, so it is necessary to change the setting “Valid” in advance in order to perform 4th fan speed setting
with the central control.
When indoor unit is operating at 4th fan speed, the fan speed mode displayed on SL4-AE (SL4-BE) shows the 4th fan mode even though its setting is
“Invalid”. (Changing the 4th fan speed setting “Valid” or “Invalid” can be done with “FUNCTION SETTING” screen on SL4-AE (SL4-BE).)
Item Description
RUN/STOP
Operation mode
Temperature setting
Fan speed
Fan direction
Filter reset
Error reset
No.
1
2
3
4
5
6
7
8
Lock/Unlock settings enabled in
Function Setting of remote controller.
Performs operation or stop control.
Sets Auto
(1)
, Cool, Dry, Fan or Heat.
Sets temperature in the range of 18 ~ 30˚C (0.5˚C interval )
(2)
Sets 4
th
(4)
, 3
rd
, 2
nd
, 1
st
, Auto speed.
Sets the auto swing ON/OFF and positions 1 ~ 4.
Controls the filter sign reset.
Puts out the errer sign with the RUN or STOP operation.
Sets the permission/prohibition based on remote controller function.
Sets the permission/prohibition for RUN/STOP control, operation mode setting,
temperature setting or respective functions.
(3)
To make the 4th fan speed operation “Able”, indoor unit model KXE6D or newer, SC-ADNA-E or newer are required.
Definitions of new and previous Super Links (new and previous SL)
New Super Link (new SL): All units connected to the network are models compatible with New Super Link
(KXE6 model or later models. Central control and I/F are from “N” models.) and
SL setting is unchanged from shipment (“New” or “AUTO”).
Previous Super Link (previous SL): Units do not meet the conditions of New SL. When even a single unit connected to
the network is an earlier model than KXE4 or the connected model is not compatible
with new SL.
Use the “Function setting” screen of main unit to set new or previous Super Link (new or previous SL).
When the connecting network consists of previous Super Link, it is necessary to change the selection.