Specifications

-
15
-
’13 • SC-T-192
This software supports.
Input to SC-SL4-BE
SC-SL4-BE
(Save)
(Text format)
Conversion
(Text format)
(Save)
a. (Group) Definition file (CSV format)
(Group name, Group composition)
b. Monthly data file (CSV format)
b-1: Daily operating time (minutes), calculated value of the air
conditioner for each period (the basis period and the
overtime), in the Super Link system
b-2: Daily cumulative pulses from meters (#1 - #8) for each
period
c. The daily energy consumption of air conditioners for each meter
group (PI1 - PI8)
d. The daily operating time (minutes) and the energy consumption
for each air conditioner
e. The daily operating time (minutes) and the daily energy
consumption for each air conditioner group (Group#1 -
Group#144)
f. The monthly operating time (hour) and the energy consumption
for each air conditioner group in the specified period.
iii) Pulse meter (electricity) group definition
iv) Pulse constant definition (kWh/pulse)
v) Setting of the calculation period
(the end of the month, the 20th of the month, or etc.)
USB Memory
(Binary format)
vi) Group definition for each tenant
vii) Setting of energy charge (the unit price and the basic charge
of electricity
viii) The sheet form of a bill
Customer processing
Calculating the air conditioner’s energy charge.
Printing out the bill of a tenant.
1. Calculates the daily energy consumption
of air conditioners for each meter group.
2. Calculates the daily operating time and the
daily energy consumption for each air
conditioner.
3. Calculates the daily operating time and the
daily energy consumption for each air
conditioner group.
4. Calculates the daily operating time and the
daily energy consumption for each air
conditioner group in the specified period.
Read the “frequency of
pulse input”, “RUN/STOP
of each indoor unit”,
“answer Hz of each indoor
unit” every minute.
The energy consumption
calculated by this equipment
does not conform to OIML.
Accumulated daily pulse counts
Accumulated pulse counts are renewed
every minute accoding to the
following calulation method
(= pulse counts accumulated up to now
+ frequency of pulse input this time)
Accumulated daily operating volume
Accumulated operating volume of each
indoor unit is renewed every minute
according to the following calulation
method.
(= operating volume accumulated up to
now + frequency of pulse input this time)
Air conditoner capacity (kW) input
Program block setting (1 - 16)
Group setting (1 - 144)
Proportional distribution calculation
method (defined by air conditioner)
(d) Software overview (SL3N-BE Utility)
SL3N-BE Utility calculates the amount of energy consumption with air conditioners running data saved by SC-SL4-BE. The
amount of energy consumption is divided proportionally day by day according to the operating ratio of the air conditioner, and
it is calculated as the group total amount of energy consumption for every period.
1) Flow of data processing