2.5.2 MELSEC-AnA (CPU)
Bit Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input Relay X X 0 - 7FF R
(*1)
Output Relay Y Y 0 - 7FF R/W
(*1)
Internal Relay M M 0 - 8191 R/W
Link Relay B B 0 - 7FF R/W
(*1)
Latch Relay L L 0 - 8191 R/W
Timer (contact) TS T 0 - 2047 R
Timer (coil) TC T 0 - 2047 R/W
Counter (contact) CS C 0 - 1023 R
Counter (coil) CC C 0 - 1023 R/W
Special Internal Relay SM SM 9000 - 9255 R
Annunciator F F 0 - 2047 R/W
Word Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input Relay WX X 0 - 7F0 R
(*1)(*2)
Output Relay WY Y 0 - 7F0 R/W
(*1)(*2)
Internal Relay WM M 0 - 8176 R/W
(*2)
Link Relay WB B 0 - 7F0 R/W
(*1)(*2)
Latch Relay WL L 0 - 8176 R/W
(*2)
Timer
(current value)
TN T
0 - 2047 R
Counter (current
value)
CN C
0 - 1023 R
Data Register D D 0 - 6143 R/W
Link Register W W 0 - FFF R/W
(*1)
Annunciator WF F 0 - 2032 R/W
(*2)
Special Internal Relay WSM SM 9000 - 9240 R
(*2)
Special Register SD SD 9000 - 9255 R
(*1) Set this device using hexadecimal.