Hardware manual

Chapter 2 Connection to a PLC
2-68
PLC Settings
Item setteing notes
Network type Ethernet (*1)
Starting I/O No. 0020 (*2)
NetworkNo. 1 (*2)
Total stations - -
Group No. 0 (*2)
Station No. 1 (*2)
network
parameter
Mode On line (*1)
Communication data code Binary code (*1)
Initial Timing Always wait for OPEN (*1)
Input format Decimal (*2)
IP Address
IP address Set IP Address of PLC (*2)
Send frame setting Ethernet (*1)
Enable Write at RUN time Check mark(enable) (*1)
Operation
Setting
TCP Existence confirmation
setting
Use the KeepAlive (*1)
Protocol TCP/IP (*1)
Open system Unpassive open (*1)
Fixed buffer Send (*1)
Fixed buffer communication Procedure exist (*1)
Pairing open No pairs (*1)
Existence confirmation No confirm (*1)
Local station Port No. set an arbitrary port number (*2)(*3)
Destination IP address - -
Open Setting
Dest. Port No. - -
Refer to the Q Corresponding Ethernet Interface Module Users Manual or Q Corresponding
Ethernet Interface Module User’s Manual for detail.
(*1) The setting of the above-mentioned is recommended.
(*2) Set it according to the environment.
(*3) MICRO/I is set by the decimal number though PLC is set by the hexadecimal number.