Hardware manual

Chapter 2 Connection to a PLC
2-62
Connection Diagram 2-10: MELSEC-FX Series CPU (RS-485) to MICRO/I
PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG1F
Terminal
HG2F/
3F/4F
HG2S
FG Cover - 1 1
TERM - - 9 -
7 SDA RDA(RD+) 2 3 10 32
4 SDB RDB(RD-) 7 4 16 33
2 RDA SDA(SD+) 1 1 11 30
1 RDB SDB(SD-) 6 2 15 31
3 SG CS- 9 - 18 37
6 SG RS- 8 - 19 35
CS+ 4 - 21 36
RS+ 3 - 22 34
Cover Shield SG 5 5 7 29
D-sub, 9P connector socket type/Terminal block (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
Mini DIN 8P Connector
Shield Wire
Internal
termination
resistor
330-Ohm
- There is no pin No. corresponding to TERM on the HG1F/HG2S. When inserting a
termination resistor, use a communication switch. For the setting of the switch, refer to "3
Important Points Regarding Wiring" in Chapter 1.
When you use the Terminal Block type of HG1F, make sure to configure the Hardware Flow
control to NONE because the HG1F doesn’t have control lines.