Hardware manual
2 Mitsubishi
2-57
Chap.2
Connection Diagram 2-4: PLC, 2-port Adapter to MICRO/I
PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG1F
Terminal
HG2F/
3F/4F
HG2S
2 RD+ FG Cover - 1 1
15 RD- TERM - - 9 -
3 SD+ RDA(RD+) 2 3 10 32
16 SD- RDB(RD-) 7 4 16 33
4 CS+ SDA(SD+) 1 1 11 30
17 CS- SDB(SD-) 6 2 15 31
5 RS+ CS- 9 - 18 37
18 RS- RS- 8 - 19 35
7 SG CS+ 4 - 21 36
8 SG RS+ 3 - 22 34
20 SG 5 5 7 29
21
Internal
termination
resistor
330-Ohm
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
D-sub, 25P connector socket type
(unit side)
Shield Wire
- In case of HG2F/3F/4F a connection cable is available (part number: HG9Z-3C165).
- In case of HG1F a connection cable is available (part number: HG9Z-XC255).
- There is no pin No. corresponding to TERM on the HG1F/HG2S. When inserting a
termination resistor, use a communication switch. For the setting of the switch, refer to "3
Important Points Regarding Wiring" in Chapter 1.
When you connect to the CPU port of MELSEC-A series and MELSEC-FX series of
Mitsubishi Electric, use D-sub 9Pin connector, NOT the Terminal Block type.