Chapter 2 Connection to a PLC
2-36
1.4.4 OpenNet Controller,MICROSmart/MICROSmart Pentra ( uses Web
Server Unit )
Set following Items in Project Settings Dialog.
Item Setting
IP Address ( for HG ) Set the IP Address for MICRO/I.
(Set the Item in Communication Interface tab.)
Subnet Mask Set the Subnet Mask for MICRO/I.
(Set the Item in Communication Interface tab.)
Default Gateway Set the Default Gateway for MICRO/I.
(Set the Item in Communication Interface tab.)
IP Address ( Web Server Unit ) Set the IP Address for Web Server Unit.
(Set the Item in Host I/F network tab.)
Port Number ( Web Server Unit ) Set the Port Number for Web Server Unit.
(Set the Item in Host I/F network tab.)
When connecting an OpenNet Controller to the MICRO/I, you must set the OpenNet
Controller special Internal Relay M8014 to on.