Hardware manual

Chapter 2 Connection to a PLC
2-32
Connection Diagram 1-7: MICROSmart/MICROSmart Pentra (RS-232C Port 1)
to MICRO/I
PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG2F/
3F/4F
HG2S
1 NC FG 1 1 1
2 NC SD 2 2 30
3 SD RD 3 3 32
4 RD RS 9 4 34
5 NC CS 6 5 36
6 SG NC -
-
7 SG SG 7 7 29
8 NC NC - 8 -
Cover Shield ER - 20 -
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
Mini DIN8P
Shield Wire
In case of HG2F/3F/4Fa connection cable is available (part number: FC4A-KC2C).
The connection diagram 1-7 is not same as FC4A-KC2C. But both diagrams are available.
Refer to the Hardware Manual about the connection diagram of FC4A-KC2C.
In case of HG1F a connection cable is available (part number: FC4A-KC1C).
The connection diagram 1-7 is not same as FC4A-KC1C. But both diagrams are available.