Hardware manual

Chapter2 Connection to a PLC
2-304
Connection Diagram 17-2: FA-M3 F3LC11-2N
MICRO/I
PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG1F
Terminal
HG2F/
3F/4F
HG2S
- FG FG Cover - 1 1
- SDB TERM - - 9 -
- SDA RDA(RD+) 2 3 10 32
- RDB RDB(RD-) 7 4 16 33
- RDA SDA(SD+) 1 1 11 30
- SG SDB(SD-) 6 2 15 31
CS- 9 - 18 37
RS- 8 - 19 35
CS+ 4 - 21 36
RS+ 3 - 22 34
SG 5 5 7 29
Internal
termination
resistor
330-Ohm
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
Screw terminal block
Shield Wire
- There is no pin No. corresponding to TERM on the HG1F/HG2S. When inserting a
termination resistor, use a communication switch. For the setting of the switch, refer to "3
Important Points Regarding Wiring" in Chapter 1.
In MICRO/I and PLC, the name of A pole and B pole is reverse.
When you use the Terminal Block type of HG1F, make sure to configure the Hardware Flow
control to NONE because the HG1F doesn’t have control lines.