13.5 Usable Devices
Types of devices supported by the MICRO/I and their ranges are shown below.
・ Bit Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input X X 0 - 511F R (*1)
Output Y Y 0 - 511F R/W (*1)
Internal Relay R R 0 - 886F R/W (*1)
Special Internal relay RE R 9000 - 910F R (*1)
Link Relay L L 0 - 639F R/W (*1)
Timer T T 0 - 3071 R Dec
Counter C C 0 - 3071 R Dec
Error alarm relay E E 0 - 2047 R Dec
・ Word Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input WX WX 0 - 00511 R Dec
Output WY WY 0 - 00511 R/W Dec
Internal Relay WR WR 0 - 00886 R/W Dec
Special Internal relay WRE WR 900 - 00910 R Dec
Link Relay WL WL 0 - 00639 R/W Dec
Timer, Counter
(Elapsed value)
EV EV 0 - 03071 R Dec
Timer, Counter
(Set value)
SV SV 0 - 03071 R/W Dec
Data register DT DT 0 - 99999 R/W Dec
Link data register LD LD 0 - 08447 R/W Dec
File register FL FL 0 - 32764 R/W Dec(*2)
(*1) 3 figures of higher ranks are expressed by decimal,
and 1 figure of low ranks is expressed by hexadecimal.
(*2) In FP2SH, the contents of a bank 0 are written.