Hardware manual
Chapter 2 Connection to a PLC
2-26
1.3 Connection Diagram
The connector types given in the Connection Diagrams are for the unit and not the cable.
For details regarding wiring, refer to "3 Important Points Regarding About Wiring" in
Chapter 1.
Connection Diagram 1-1: FA-3S (PF3S-SIF2) to MICRO/I
PLC(RS-232C) HG1F/2F/2S/3F/4F(RS-232C)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG2F/
3F/4F
HG2S
1 CD FG 1 1 1
2 RD SD 2 2 30
3 SD RD 3 3 32
4 ER RS 9 4 34
5 GND CS 6 5 36
6 DR NC -
6
-
7 RS SG 7 7 29
8 CS NC - 8 -
9 RI ER - 20 -
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
D-sub, 9P connector plug type
(unit side)
Shield Wire
In case of HG2F/3F/4F a connection cable is available (part number: PF3S-KS1).
In case of HG1F a connection cable is available (part number: XC115).