Hardware manual
Chapter2 Connection to a PLC
2-210
Connection Diagram 10-3
:
TCmini (RS-485) - MICRO/I
PLC(RS-485/422) HG1F/2F/2S/3F/4F(RS-485/422)
Pin No.
Pin No.
Name
Name
HG1F
Connector
HG2F/
3F/4F
HG2S HG2S
1 TDA FG Cover - 1 1
2 TDB TERM - - 9 -
3 RDA(A) RDA(RD+) 2 3 10 32
4 RDB(B) RDB(RD-) 7 4 16 33
5 GND SDA(SD+) 1 1 11 30
6 P5V SDB(SD-) 6 2 15 31
7 FG CS- 9 - 18 37
RS- 8 - 19 35
CS+ 4 - 21 36
RS+ 3 - 22 34
SG 5 5 7 29
D-sub, 9P connector socket type (HG1F)
D-sub, 25P connector socket type (HG2F/3F/4F)
D-sub, 37P connector plug type (HG2S)
Internal
termination
resistor
330-Ohm
Shield Wire
- There is no pin No. corresponding to TERM on the HG1F/HG2S. When inserting a
termination resistor, use a communication switch. For the setting of the switch, refer to "3
Important Points Regarding Wiring" in Chapter 1.
When you use the Terminal Block type of HG1F, make sure to configure the Hardware Flow
control to NONE because the HG1F doesn’t have control lines.