Hardware manual

Chapter2 Connection to a PLC
2-204
Counter contact P1C C 0 - 1FF R
Extended input EX EX 0 - 7FF R/W
Extended output EY EY 0 - 7FF R/W
Extended Internal
relay
EM EM 0 - 1FFF R/W
Extended keep-relay EK EK 0 - FFF R/W
Extended link relay EL EL 0 - 1FFF R/W
Extended special
relay
EV EV 0 - FFF R/W
Extended edge
detection
EP EP 0 - FFF R/W
Extended timer
contact
ET ET 0 - 7FF R
Extended counter
contact
EC EC 0 - 7FF R
Extended input GX GX 0 - FFFF R/W (*4)
Extended output GY GY 0 - FFFF R/W (*4)
Extended Internal
relay
GM GM 0 - FFFF R/W (*4)
Word Device
Device Symbol
Device Name
HG PLC
Address Range
Read
/Write
Address
Gradual
Input WX X 0 - 7F R/W
Output WY Y 0 - 7F R/W
Internal relay WM M 0 - 7F R/W (*1)
Keep-relay WK K 0 - 2F R/W (*1)
Link relay WL L 0 - 7F R/W (*1)
Timer contact WT T 0 - 1F R (*1)
Counter contact WC C 0 - 1F R (*1)
Present value register N N 0 - 1FF R (*1)
Data register D D 0 - 2FFF R/W (*1)
Link register R R 0 - 7FF R/W (*1)
Special register S S 0 - 3FF R/W (*1)
File register B B 0 - 1FFF R/W (*1) (*2)
Internal relay P3WM M 0 - 7F R/W
Keep-relay P3WK K 0 - 2F R/W