7.5 Usable Devices
The types of devices handles by the MICRO/I and their ranges are shown below.
Bit Device
WindO/I-NV2 Device Name
R/W WindO/I-NV2 address
PLC Device Name
PLC address
Relay R/W R 0 to R 15777 00000 to 15777
Ext. Relay R/W ER 20000 to ER 75777
Relay
20000 to 75777
Timer(Contact) R T 0 to T 777 T0000 to T0777
Ext. Timer(Contact) R ET 1000 to ET 1777
Timer(Contact)
T1000 to T1777
Counter(Contact) R C 0 to C 777 C0000 to C0777
Ext. Counter(Contact) R EC 1000 to EC 1777
Counter(Contact
)
C1000 to C1777