Hardware manual

4 Allen-Bradley PLCs
2-151
Chap.2
4.6 The way to set device address when use ControlLogix, CompactLogix
series
In ControlLogix and CompactLogix series, device is set with tag name. However you have to set
with Symbol and Address format which is same as MicroLogix, SLC 500 and PLC-5 because
WindO/I-NV2 can not operate tag name directly.
You have to attach each tag names to device symbol and device address at that time.
The work is called to mapping.
4.6.1 The way of mapping
The following work is done in RS Logix 5000 software.
1.
Define some tags to communicate with MICRO/I in Controller Tags
2.
Select Logic and Map PLC/SLC Messages… on main menu in RS Logix 5000
software.
3.
Attach File Number to each tag name in PLC3,5/SLC Mapping dialog box.
4.6.2 The way to select device address in WindO/I-NV2
When select device address in WindO/I-NV2, set tag type to device symbol and set array number
to File Number.