Hardware manual
4 Allen-Bradley PLCs
2-123
Chap.2
4.4.3 PLC-5
Item Setting
Communication Interface(*1)(*2) RS-232-C/RS-485-A (4 line)
Baud Rate (bps) (*4)(*5) 1200, 2400, 4800, 9600 or 19200
Data Bits (*4)(*5) 8 (fixed)
Parity (*4)(*5) None or Even
Stop Bits (*4)(*5) 1 (fixed)
Communication Protocol (*4) Half duplex (*6)
Channel 0 Protocol (*4) DF1 Slave (*6)
Duplicate Detect (*4) OFF (*6)
Error Detect (*4) BCC (*6)
Control Line (*4) No handshaking (*6)
Network Link (*1) Data highway plus
PLC-5 Processor Station Address (*3)(*5) 00 to 77(Octal)
1770-KF2 Node Number (*1)(*5)(*7) 00 to 77(Octal)
(*1) When using the 1770-KF2 Module, select this setting using the 1770-KF2 Module DIP
switch
(*2) In the case of a direct connection to the PLC-5 Processor Module, select this setting
using the PLC-5 Processor Module DIP switch.
(*3) This setting is required regardless of whether 1770-KF2 Module is used or not. When
using the 1770-KF2 Module, select this setting using the DIP switch on PLC-5 Processor,
and in the case of a direct connection to the PLC-5 Processor Module, select using the
6200 Programming Software (Channel 0 configuration).
(*4) When using the 1770-KF2 Module, select this setting using the DIP switch on 1770-KF2
Module. In case of a direct connection to the PLC-5 Processor Module, select using the
6200 Programming Software (Channel 0 configuration).
(*5) The setting for this item must match the setting on the HG Series unit.
(*6) Be certain to select as indicated.
(*7) This selection is only necessary if you are using the Interface Module.
Setting the Station Address using WindO/I-NV2
When using the 1770-KF2 Module, select “Use 1770-KF2” checkbox in the WindO/I-NV2
Project Settings, and set “Station Address (1770-KF2)” and “Station Address (PLC5)”.
In case of direct connection to PLC5 Processor Module, do not select the “Use 1770-KF2”
checkbox. Instead select “Station Address (1770-KF2)”.
These numbers are to be set using octal for the PLC-5 and 1770-KF2, but hexadecimal for the
WindO/I-NV2.